496
SIEPCYEUOQ2V01A Q2V Technical Manual
Do not enable this parameter in these conditions:
•
Operating a motor in the middle speed range or low speed range
•
Power supply voltage is a minimum of 10% more than the motor rated voltage
When you enable this parameter, if the power supply voltage is much less than the motor rated voltage, torque
control will not be accurate.
0 : Disabled
1 : Enabled
■
C3-16: Vout Limit Start Level
No.
(Hex.)
Name
Description
Default
(Range)
C3-16
(0261)
Expert
Vout Limit Start Level
Sets the modulation factor that starts the output voltage limit operation when
C3-05 = 1 [Vout
Limit Selection = Enabled]
.
90.0%
(70.0 - 90.0%)
■
C3-17: Vout Limit Max Level
No.
(Hex.)
Name
Description
Default
(Range)
C3-17
(0262)
Expert
Vout Limit Max Level
Sets the modulation factor used with
C3-18 [Vout Limit Level]
for the output voltage limit
operation when
C3-05 = 1 [Vout Limit Selection = Enabled]
.
100.0%
(85.0 - 100.0%)
■
C3-18: Vout Limit Level
No.
(Hex.)
Name
Description
Default
(Range)
C3-18
(0263)
Expert
Vout Limit Level
Sets the maximum drop width of the voltage reference when
C3-05 = 1 [Vout Limit Selection =
Enabled]
.
90.0%
(50.0 - 100.0%)
■
C3-21: M2 Slip Comp Gain
No.
(Hex.)
Name
Description
Default
(Range)
C3-21
(033E)
RUN
M2 Slip Comp Gain
Sets the gain for the motor 2 slip compensation function. Usually it is not necessary to change this
setting.
Determined by E3-01
(0.0 - 2.5)
Note:
Correctly set these parameters before changing the slip compensation gain:
•
E4-01 [M2 Rated Current (FLA)]
•
E4-02 [M2 Rated Slip]
•
E4-03 [M2 No-Load Current]
Use these settings to adjust this parameter as necessary:
•
If the motor speed is slower than the frequency reference, increase C3-01 in 0.1 unit increments.
•
If the motor speed is higher than the frequency reference, decrease the setting of this parameter in 0.1-unit
increments.
■
C3-22: M2 Slip Comp DelayTime
No.
(Hex.)
Name
Description
Default
(Range)
C3-22
(0241)
RUN
M2 Slip Comp DelayTime
Sets the slip compensation delay time for motor 2 when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
Determined by E3-01
(0 - 10000 ms)
Use these settings to adjust this parameter as necessary:
•
When the speed is not stable, increase the setting.
•
When the slip compensation response is too slow, decrease the setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...