SIEPCYEUOQ2V01A Q2V Technical Manual
509
•
When you set the voltage input of analog inputs from terminals AI1 and AI2 to 0 V to 10 V (Lower Limit at 0)
Procedure
Configuration
Parameter
Task Contents
1
Reference 1
1.
Sets
b1-01 = 1 [Freq. Ref. Sel. 1 = Analog Input]
.
2.
Sets
H3-02 = 3 [AI1 Function Selection = FrqBIAS Frq]
.
3.
Sets
H3-01 = 0 [AI1 Signal Level Select = 0 to 10V (Lower Limit at 0)]
.
2
Reference 2
1.
Sets
H3-10 = 1 [AI2 Function Selection = AuxFreqRef1]
.
2.
Sets
H3-09 = 0 [AI2 Signal Level Select = 0 to 10V (Lower Limit at 0)]
.
3
Signal type of analog input
Set DIP switch S1 on the control circuit board to the V-side (voltage) to set terminal AI2 only for voltage input.
Note:
Set this before you energize the drive.
4
Reference 3
Sets the value of
d1-03 [Reference 3]
.
5
Reference 4
Sets the value of
d1-04 [Reference 4]
.
6
Reference 5
Sets the value of
d1-05 [Reference 5]
.
7
Jog Reference
Sets
d1-17 [Jog Reference]
to the jog speed.
8
External digital input (3
inputs)
Set the
Multi-Step Speed Reference 1 to 3 [H1-xx = A, B, C]
to one of the MFDI terminals DI1 to DI7.
9
JOG command
Set the
Jog Reference [H1-xx = 6]
to one of the MFDI terminals DI1 to DI7.
Use the Maximum 17-Step Speed with All Digital Inputs
This section is the procedure to set the 17-step speeds (17 types of frequency references) without an analog input.
Procedure
Configuration
Parameter
Task Contents
1
Analog reference
1.
Sets
H3-02 = 0 [AI1 Function Selection = Through Mode]
, and disables the analog reference.
2.
Sets
H3-10 = 0 [AI2 Function Selection = Through Mode]
, and disables the analog reference.
2
Reference 2 to 16
Sets the values of
d1-02 to d1-16 [Reference 2 to Reference 16]
.
3
Jog Reference
Sets
d1-17 [Jog Reference]
to the jog speed.
4
External digital input (4
inputs)
Set
Multi-Step Speed Reference 1 to 4 [H1-xx = A, B, C, D]
to one of the MFDI terminals DI1 to DI7.
5
JOG command
Set the
Jog Reference [H1-xx = 6]
to one of the MFDI terminals DI1 to DI7.
Multi-step Speed Operation Combinations
Refer to
and
for information about multi-step speed reference combinations. The
selected frequency reference changes when the combination of digital input signals from an external source
changes.
Table 12.26 Multi-step Speed Reference and MFDI Terminal Combinations
Related Parameters
MultSpd Ref1
H1-xx = A
MultSpd Ref2
H1-xx = B
MultSpd Ref3
H1-xx = C
MultSpd Ref4
H1-xx = D
Jog Reference
H1-xx = 6
Reference 1 (set in
b1-01
)
OFF
OFF
OFF
OFF
OFF
Reference 2 (
d1-02
or
terminals AI1, AI2)
ON
OFF
OFF
OFF
OFF
Reference 3 (
d1-03
or
terminals AI1, AI2)
OFF
ON
OFF
OFF
OFF
Reference 4 (
d1-04
)
ON
ON
OFF
OFF
OFF
Reference 5 (
d1-05
)
OFF
OFF
ON
OFF
OFF
Reference 6 (
d1-06
)
ON
OFF
ON
OFF
OFF
Reference 7 (
d1-07
)
OFF
ON
ON
OFF
OFF
Reference 8 (
d1-08
)
ON
ON
ON
OFF
OFF
Reference 9 (
d1-09
)
OFF
OFF
OFF
ON
OFF
Reference 10 (
d1-10
)
ON
OFF
OFF
ON
OFF
Reference 11 (
d1-11
)
OFF
ON
OFF
ON
OFF
Reference 12 (
d1-12
)
ON
ON
OFF
ON
OFF
Reference 13 (
d1-13
)
OFF
OFF
ON
ON
OFF
Reference 14 (
d1-14
)
ON
OFF
ON
ON
OFF
Reference 15 (
d1-15
)
OFF
ON
ON
ON
OFF
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...