F6-63: DNet Network MAC ID
No.
(Hex.)
Name
Description
Default
(Range)
F6-63
(03DE)
DNet Network MAC ID
Sets the function to see the actual DeviceNet MAC address using the keypad. This parameter
functions as a monitor only.
0
(0 - 63)
■
F6-64 to F6-67: DynOut.Ass109 P1 to P4
No.
(Hex.)
Name
Description
Default
(Range)
F6-64 to F6-67
(03DF - 03E2)
DynOut.Ass109 P1 to P4
Sets Configurable Outputs 1 to 4 written to the Modbus register.
0000h
(0000h - FFFFh)
■
F6-68 to F6-71: DynIn.Ass159 P1 to 4
No.
(Hex.)
Name
Description
Default
(Range)
F6-68 to F6-71
(03E3, 03E4,
03C7, and 03C8)
DynIn.Ass159 P1 to 4
Sets Configurable Inputs 1 to 4 written to the Modbus register.
0000h
(0000h - FFFFh)
■
F6-72: PowerLink Address
No.
(Hex.)
Name
Description
Default
(Range)
F6-72
(081B)
PowerLink Address
Sets the node ID for PowerLink communication.
0
(0 - 255)
■
F7-01: IP Address 1
No.
(Hex.)
Name
Description
Default
(Range)
F7-01
(03E5)
IP Address 1
Sets the first octet of the IP Address for the device that is connecting to the network. Restart the
drive after you change this parameter.
192
(0 - 255)
Note:
When
F7-13 = 0 [Addr Mode@Startup = Static]
:
•
Use parameters
F7-01 to F7-04
to set the IP Address. Be sure to set a different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
■
F7-02: IP Address 2
No.
(Hex.)
Name
Description
Default
(Range)
F7-02
(03E6)
IP Address 2
Sets the second octet of the IP Address for the device that is connecting to the network. Restart the
drive after you change this parameter.
168
(0 - 255)
Note:
When
F7-13 = 0 [Addr Mode@Startup = Static]
:
•
Use parameters
F7-01 to F7-04
to set the IP Address. Be sure to set a different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
■
F7-03: IP Address 3
No.
(Hex.)
Name
Description
Default
(Range)
F7-03
(03E7)
IP Address 3
Sets the third octet of the IP Address for the device that is connecting to the network. Restart the
drive after you change this parameter.
1
(0 - 255)
Note:
When
F7-13 = 0 [Addr Mode@Startup = Static]
:
•
Use parameters
F7-01 to F7-04
to set the IP Address. Be sure to set a different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...