566
SIEPCYEUOQ2V01A Q2V Technical Manual
12.7
H: TERMINALS
H parameters
set functions for external input and output terminals.
◆
H1: DIGITAL INPUTS
H1 Parameters
set the MFDI terminal functions.
■
H1-01 to H1-07 Terminal DI1 to DI7 Function Selection
The drive has 7 MFDI terminals. These are the drive default settings and functions.
Table 12.37 MFDI Default Settings and Functions
No.
Name
Default
Function
H1-01
DI1 Function Selection
1 (0)
Forward Run
H1-02
DI2 Function Selection
2 (0)
Reverse Run
H1-03
DI3 Function Selection
24
ExF NO-AlCoast
H1-04
DI4 Function Selection
7B
Fault Reset
H1-05
DI5 Function Selection
A (5)
MultSpd Ref1
H1-06
DI6 Function Selection
B (A)
MultSpd Ref2
H1-07
DI7 Function Selection
6 (B)
Jog Reference
*1
The value in parentheses identifies the default setting when you set
A1-03 = 3330 [Init Parameters = 3-Wire Initialization]
.
Refer to
and use
H1-xx [MFDI Function Select]
to set the function.
Table 12.38 MFDI Setting Values
Setting Value
Function
Reference
0
Through Mode
1
Forward RUN (2-Wire)
2
Reverse RUN (2-Wire)
3
Run Command (2-Wire Sequence 2)
4
FWD/REV (2-Wire Sequence 2)
5
3-Wire Sequence
6
Jog Reference Selection
7
Forward Jog
8
Reverse Jog
9
External Reference 1/2 Selection
A
Multi-Step Speed Reference 1
B
Multi-Step Speed Reference 2
C
Multi-Step Speed Reference 3
D
Multi-Step Speed Reference 4
E
Add Offset Frequency 1 (d7-03)
F
Add Offset Frequency 2 (d7-03)
10
Add Offset Frequency 3 (d7-03)
11
LOCAL/REMOTE Selection
12
Analog Terminal Enable Selection
15
Reverse Rotation Identifier
16
Reference Sample Hold
17
Accel/Decel Ramp Hold
18
Accel/Decel Time Selection 1
19
Accel/Decel Time Selection 2
1A
Drive Enable
1B
Baseblock Command (N.O.)
Setting Value
Function
Reference
1E
Baseblock Command (N.C.)
20 to 2F
External fault
30
DC Injection Braking Command
32
High Slip Braking (HSB)
34
Fast Stop (N.O.)
35
Fast Stop (N.C.)
3E
Short Circuit Braking (N.O.)
3F
Short Circuit Braking (N.C.)
40
KEB Ride-Thru 1 Activate (N.C.)
41
KEB Ride-Thru 1 Activate (N.O.)
42
KEB Ride-Thru 2 Activate (N.C.)
43
KEB Ride-Thru 2 Activate (N.O.)
44
Field Weakening
45
ASR Gain (C5-03) Select
46
ASR Integral Reset
60
Timer Function
61
Motor 2 Selection
62
Up Command
63
Down Command
65
Up 2 Command
66
Down 2 Command
67
Speed Search from Fmax
68
Speed Search from Fref
6A
PID Disable
71
PID Integrator Reset
72
PID Integrator Hold
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...