582
SIEPCYEUOQ2V01A Q2V Technical Manual
Note:
Refer to
“
d4-10: Up/Down Freq Lower Limit Select
”
for details.
shows an example of how Up/Down command operates. In this example, the lower limit value of the
frequency reference is set in
d2-02
.
shows the time chart when Freq Reference
Retention Select [d4-
01]
is enabled and disabled.
Figure 12.72 Up/Down Command Time Chart
■
63: Down Command
Setting Value
Function
Description
63
Down Command
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set
Setting 62 [Up
Command]
.
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
Note:
•
If you set only the Up command or only the Down command, the drive will detect
oPE03 [Multi-Function Input Setting Err]
.
•
If you set two or more of these functions at the same time, the drive will detect
oPE03
:
–
Up/Down command
–
Accel/Decel Ramp Hold
–
Reference Sample Hold
–
Offset Frequency 1, 2, 3 addition
–
Up/Down 2 Command
•
The Up/Down command does not function in these conditions:
–
b1-01 = 2, 3 [Freq. Ref. Sel. 1 = Modbus, Option PCB]
–
b1-02 ≠ 1 [Run Comm. Sel 1 ≠ Analog Input]
–
Drive is in LOCAL mode
–
Set to
b1-15 [Freq. Ref. Sel. 2]
by use of
H1-xx = 9 [MFDI Function Select = Ext Ref 1/2]
When you enter the UP command, the frequency reference increases. When you enter the Down command, the
frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down
command, the drive will ignore these frequency references:
•
Frequency reference from Keypad
[b1-01 = 0]
•
Frequency reference from Analog Input
[b1-01 = 1]
•
Frequency reference from Pulse Train Input
[b1-01 = 4]
■
65: Up2 Command
Setting Value
Function
Description
65
Up2 Command
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is activated. Set this
function and
H1-xx = 66 [Dw2 Command]
together.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...