590
SIEPCYEUOQ2V01A Q2V Technical Manual
■
H2-07: Mbus Reg1 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-07
(0B3A)
Mbus Reg1 Address Select
Sets the address of the Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to
ModbusReg 1 [H2-01 to H2-03 = 67]
and uses the bit in
H2-08
[Mbus Reg1 Bit Select]
.
■
H2-08: Mbus Reg1 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-08
(0B3B)
Mbus Reg1 Bit Select
Sets the bit of the Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to
ModbusReg 1 [H2-01 to H2-03 = 67]
and uses the address in
H2-07
[Mbus Reg1 Address Select]
.
■
H2-09: Mbus Reg2 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-09
(0B3C)
Mbus Reg2 Address Select
Sets the address of the Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to
ModbusReg 1 [H2-01 to H2-03 = 67]
and uses the bit in
H2-10
[Mbus Reg2 Bit Select]
.
■
H2-10: Mbus Reg2 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-10
(0B3D)
Mbus Reg2 Bit Select
Sets the bit of the Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to
ModbusReg 1 [H2-01 to H2-03 = 67]
and uses the address in
H2-09
[Mbus Reg2 Address Select]
.
■
H2-20: Compare1 Mon.Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-20
(1540)
Compare1 Mon.Selection
Sets the monitor number for comparator 1. Set the
x-xx
part of the
Ux-xx [Monitor]
. For example,
set
H2-20 = 102
to monitor
U1-02 [Output Frequency]
.
102
(000 - 999)
Note:
•
For information on the comparator function, refer to
and
•
The configurable monitor changes when the control method changes.
■
H2-21: Compare1 Low Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-21
(1541)
Compare1 Low Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in
H2-20 [Compare1 Mon.Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-22: Compare1 Up Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-22
(1542)
Compare1 Up Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in
H2-20 [Compare1 Mon.Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...