SIEPCYEUOQ2V01A Q2V Technical Manual
591
Note:
For information on the comparator function, refer to
and
■
H2-23: Compare1 Hysteresis
No.
(Hex.)
Name
Description
Default
(Range)
H2-23
(1543)
Compare1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in
H2-20 [Compare1 Mon.Selection]
.
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to
and
■
H2-24: Compare1 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-24
(1544)
Compare1 On-Delay Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to
and
■
H2-25: Compare1 Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-25
(1545)
Compare1 Off-Delay Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to
and
■
H2-26: Compare2 Mon.Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-26
(1546)
Compare2 Mon.Selection
Sets the monitor number for comparator 2. Set the
x-xx
part of the
Ux-xx [Monitor]
. For example,
set
H2-26 = 103
to monitor
U1-03 [Output Current]
.
103
(000 - 999)
Note:
•
The configurable monitor changes when the control method changes.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can set the terminal output level from the PLC
through Modbus communications or the communication option.
•
For information on the comparator function, refer to
and
■
H2-27: Compare2 Low Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-27
(1547)
Compare2 Low Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in
H2-26 [Compare2 Mon.Selection]
.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-28: Compare2 Up Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-28
(1548)
Compare2 Up Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in
H2-26 [Compare2 Mon.Selection]
.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...