SIEPCYEUOQ2V01A Q2V Technical Manual
609
Example
Analog Input
Settings
Terminal AI1 Setting
Frequency Reference
Frequency
Reference When
You Adjust the
Gain Setting
•
H3-02 = 1 [AI1 Function
Selection= AuxFreqRef1]
•
H3-03 = 200.0 [AI1 Gain Setting =
200%]
•
H3-04 = 0.0 [AI1 Bias Setting =
0.0%]
•
When you input a 10 V signal, the frequency reference will be 200%.
•
When you input a 5 V signal, the frequency reference will be 100%.
When you input a 5 V or more signal,
E1-04 [Max Output Frequency]
will limit the drive output and the frequency
reference will be 100%.
Frequency
Reference When
You Set the Bias
to a Negative
Number
•
H3-02 = 1 [AuxFreqRef1]
•
H3-03 = 100.0 [100.0%]
•
H3-04 = -25.0 [-25.0%]
•
When you input a 0 V signal, the frequency reference will be -25%.
•
When
H3-01 = 0 [AI1 Signal Level Select = 0 to 10V (Lower Limit at 0)]
–
When you input a 0 V to 2 V signal, the frequency reference will be 0%.
–
When you input a 2 V to 10 V signal, the frequency reference will be 0% to 100%.
•
When
H3-01 = 1 [0 to +10 V (Without Lower Limit)]
–
When you input a 0 V to 2 V signal, it enables signals of positive and negative polarities and the motor
rotates in reverse.
■
Modbus Multi-Function AI1 to 3 Function Selection
You can set the MFAI function to Modbus register
15C1 to 15C3 (Hex.) [Mbus Reg 15C1h through 15C3h Input
Function]
. Use
H3-40 to H3-42 [15C1h Input Function to 15C3h Input Function]
to set the function and use
H3-
43 [Mbus In FilterTime Const]
to set the input filter.
Table 12.48 Modbus Multi-Function AI Command Register
Register No.
(Hex.)
Name
Parameter
15C1
Mbus Reg 15C1h Input Function
-32767 - +32767
H3-40
15C2
Mbus Reg 15C2h Input Function
-32767 - +32767
H3-41
15C3
Mbus Reg 15C3h Input Function
-32767 - +32767
H3-42
*1
Set as 100% = 4096.
Figure 12.90 Functional Block Diagram for Modbus Multi-Function AI Command 1
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...