614
SIEPCYEUOQ2V01A Q2V Technical Manual
•
If you use this function to set the analog input value as the master frequency reference, set
b1-01 = 1 [Freq. Ref.
Sel. 1 = Analog Input]
. This setting value is the default value for terminals AI1 and AI2.
•
The frequency reference is the sum of the input values for terminals AI1 and AI2 when they are used at the
same time. For example, when a 20% bias is input to terminal AI2 while a frequency reference of 50% is input
from terminal AI1, the calculated frequency reference will be 70% of the maximum output frequency.
■
5: Freq Gain
Setting Value
Function
Description
5
Freq Gain
The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
Example: When you set frequency gain for terminal AI2
•
H3-10 = 5 [AI2 Function Selection = Freq Gain]
•
A 50% frequency gain is input to terminal AI2
•
A frequency reference of 80% is input from terminal AI1
The calculated frequency reference is 40% of the maximum output frequency.
■
6: OutVolt Bias
Setting Value
Function
Description
6
Output Voltage Bias
Set this parameter to input a bias signal to amplify the output voltage.
The gain (%) for the MFAI terminals AI1 and AI2 is 100% of the voltage class standard, which is 200 V for 200
V class drives and 400 V for 400 V class drives. The bias (%) for MFAI terminals AI1 and AI2 is 100% of the
voltage configured for
E1-05 [Max Output Voltage]
.
Note:
The gain for each terminal AI1 and AI2 is set independently with
H3-03 [AI1 Gain Setting] and H3-11 [AI2 Gain Setting]
. The bias for
each terminal AI1 and AI2 is set independently with
H3-04 [AI1 Bias Setting] and H3-12 [AI2 Bias Setting]
.
Figure 12.91 Output Voltage Bias through Analog Input
■
7: TorqCompensation
Setting Value
Function
Description
7
TorqCompensation
Enters the torque compensation value if the motor rated torque is 100%.
■
8: TorqRef/Lim
Setting Value
Function
Description
8
TorqRef/Lim
Enters the torque reference if the motor rated torque is 100%. This setting is the torque limit for speed control.
Note:
When you use
L7-01 to L7-04
and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■
9: FW Trq Lim
Setting Value
Function
Description
9
FW Trq Lim
Enters the forward torque limit if the motor rated torque is 100%.
WARNING!
Sudden Movement Hazard. Set correct torque limits for applications, for example elevator applications. If you set
torque limits incorrectly, motor torque that is not sufficient can cause damage to equipment and cause serious injury or death.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...