654
SIEPCYEUOQ2V01A Q2V Technical Manual
■
L3-38: CurLim PGain@Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-38
(11D2)
Expert
CurLim PGain@Accel
Suppresses current hunting and overshooting that occurs when the drive stalls during acceleration.
Usually it is not necessary to change this setting.
10.0
(0.0 - 100.0)
Note:
Set
L3-01 = 4 [StallP Mode@Accel = ILim Mode]
to enable this function.
■
L3-39: CurLim Filt@Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-39
(11D3)
CurLim Filt@Accel
Sets the time constant to adjust the acceleration rate when
L3-01 = 4 [StallP Mode@Accel = ILim
Mode]
. Usually it is not necessary to change this setting.
100.0 ms
(1.0 - 1000.0 ms)
Note:
Set
L3-01 = 4 [StallP Mode@Accel = ILim Mode]
to enable this function.
■
L3-40: CurLim SCurve@Acc/Dec
No.
(Hex.)
Name
Description
Default
(Range)
L3-40
(11D4)
CurLim SCurve@Acc/Dec
Sets the function to enable and disable the best S-curve characteristic used for current-limited
acceleration.
0
(0, 1)
Makes the best motor acceleration rate for start up. If you set this parameter to 1, it will make acceleration
smoother, but it can also increase the acceleration time to be longer than the set time. If the drive detects
oC
[Overcurrent]
faults immediately after acceleration starts, set this parameter.
0 : Disabled
1 : Enabled
Note:
Set
L3-01 = 4 [StallP Mode@Accel = ILim Mode]
to enable this function.
■
L3-50 StallP@Decel Mode
No.
(Hex.)
Name
Description
Default
(Range)
L3-50
(0458)
StallP@Decel Mode
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
0
(Determined by A1-02)
Note:
1. To connect a dynamic braking option (braking resistor or braking resistor unit) to the drive, set this parameter to
0 or 3
. Parameter
values
1, 2, 4, and 5
will enable Stall Prevention function during deceleration, and the dynamic braking option will not function.
2. The setting range changes when the
A1-02 [Control Method]
value changes:
•
When
A1-02 = 5 [PM OLVector]
, setting range is
0 to 2
•
When
A1-02 = 6, or 8 [PM AOLVector, or EZ Vector]
, setting range is
0, 1
.
Stall Prevention during deceleration controls the deceleration as specified by the DC bus voltage and does not let
high inertia or fast deceleration cause
ov [Overvoltage]
faults.
0 : General Purpose
The drive decelerates as specified by the deceleration time. When the DC bus voltage is more than the Stall
Prevention level, the drive stops deceleration until the DC bus voltage is less than the Stall Prevention Level. The
drive then starts to decelerate at the set deceleration time. Frequent use of Stall Prevention will help prevent
ov
faults when the deceleration time is shorter than the drive can usually accept.
Note:
The Decel Stall Prevention function will increase the deceleration time to stop and the deceleration time will be longer than the setting.
This function is not applicable for conveyor applications because the precision of the stop position is very important. As an alternative,
use a dynamic braking option in these applications.
The input voltage setting of
E1-01 [Input AC Supply Voltage]
sets the DC bus voltage level for Stall Prevention.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...