SIEPCYEUOQ2V01A Q2V Technical Manual
657
The drive follows the frequency reference and stops the motor.
2 : Run@L4-06PrevRef
The drive continues to operate at the frequency reference value set in
L4-06 [Freq.Ref@RefLoss]
. When you
return the external frequency reference value, the drive continues to operate with the frequency reference.
■
L4-06: Freq.Ref@RefLoss
No.
(Hex.)
Name
Description
Default
(Range)
L4-06
(04C2)
Freq.Ref@RefLoss
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before the drive
detected the loss.
80.0%
(0.0 - 100.0%)
Set
L4-05 = 2 [FrefLoss Det.Selection = Run@L4-06PrevRef]
to enable this parameter.
■
L4-07: SpAgree Det.Selection
No.
(Hex.)
Name
Description
Default
(Range)
L4-07
(0470)
SpAgree Det.Selection
Sets the condition that activates speed detection.
1
(1, 2)
1 : No Detect@BB
Detects the frequency while the drive is operating. When the drive turns off its output, it will not detect frequency.
2 : Always Detect
■
L4-08: Sp Agree Source Selection
No.
(Hex.)
Name
Description
Default
(Range)
L4-08
(047F)
Sp Agree Source Selection
Sets the drive to use the soft starter output frequency or the motor speed (estimation value) for
speed detection.
1
(0, 1)
0 : SFS O/P (Reference)
1 : MotSpd (ActSpeed)
The setting for
L4-08
has an effect:
•
When you set detection conditions for
oL3 [Overtorque 1]
,
oL3 [Overtorque Detection 1]
,
oL4 [Overtorque 2]
,
and
oL4 [Overtorque Detection 2]
:
–
L6-01 = 1 [Trq Det1 Select = Enabled]
and
L6-50 = 1 [Trq Det1 Type = At Underload]
–
L6-04 = 1 [Trq Det2 Select = Enabled]
and
L6-53 = 1 [Trq Det2 Type = At Underload]
•
When you use speed agreement with Q2dev.
•
When the MFDI terminals set for
H1-xx = 65, 66 [Up2 Command, Dw2 Command]
activate.
•
When you set
H2-xx [MFDO Function Select]
to these functions:
Setting Value
Function
F
SpeedAgree1
10
USpeedAgree1
11
SpeedAgree2
12
USpeedAgree2
Setting Value
Function
13
FreqDetect 1
14
FreqDetect 2
15
FreqDetect 3
16
FreqDetect 4
•
When you use these functions for Modbus monitor data:
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...