658
SIEPCYEUOQ2V01A Q2V Technical Manual
Register No.
Description
002CH
Drive Status 2
bit2
Speed agreement
1: During agreement
bit3
User-defined speed agreement
1: During agreement
bit4
Frequency Detection 1
1: Output frequency ≤ L4-01
bit5
Frequency Detection 2
1: Output frequency ≥ L4-01
004BH
U1-12 [Drive Status]
bit4
1: During speed agreement
•
When you use these functions for monitor parameters:
No.
(Hex.)
Name
Description
U1-12
(004B)
Drive Status
bit 4: During speed agreement
◆
L5: FAULT RESTART
The Auto Restart function tries to keep machines operating when the drive detects a transient fault.
The drive can do a self-diagnostic check and continue the operation after a fault. If the cause of the fault goes
away, the drive does speed search and restarts. It will not stop and the drive will not record a fault history. Use
L5-
02 [Fault@Reset Select]
to select the operation of fault relay signals during Auto Restart operation.
Sets if the drive will do Auto Restart and the number of times the drive will try to do Auto Restart in a set time. If
the number of Auto Restart tries is more than the set value during the set time, drive output shuts off and operation
stops. If this happens, remove the cause of the fault and manually restart the drive.
WARNING!
Sudden Movement Hazard. Do not use the fault restart function in hoist or lifting applications. Failure to obey can
cause death or serious injury.
The drive can do Auto Restart when these faults occur:
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Table 12.52 List of Faults during which Auto Restart is Available
Fault
Name
Parameters to Disable
Auto Restart
GF
Ground Fault
L5-08
LF
Output Phase Loss
-
oC
Overcurrent
-
oH1
Heatsink Overheat
L5-08
oL1
Motor Overload
L5-07
oL2
Drive Overload
L5-07
oL3
Overtorque Detection 1
L5-07
oL4
Overtorque Detection 2
L5-07
Fault
Name
Parameters to Disable
Auto Restart
ov
Overvoltage
L5-08
PF
Input Phase Loss
-
rH
Braking Resistor Overheat
-
rr
Dynamic Braking
Transistor Fault
-
STPo
Motor Step-Out Detected
-
Uv1
DC Bus Undervoltage
L5-08
*1
Uv1
is the target for the auto restart process when
L2-01 = 1 [RideThru@PwrLoss = Enabled]
, and L2-50 = 0, 1, 2, 3
[RidThruMode@PwrLoss = Timer Controlled, While CPU Active, KEB Mode, KEB Stop Mode].
■
L5-01: Auto-Reset Attempts
No.
(Hex.)
Name
Description
Default
(Range)
L5-01
(049E)
Auto-Reset Attempts
Sets the number of times that the drive will try to restart.
0
(0 - 10 times)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
•
The drive operates correctly for 10 minutes after a fault restart.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...