SIEPCYEUOQ2V01A Q2V Technical Manual
659
•
When you manually clear a fault after the drive triggers protective functions.
•
When you re-energize the drive.
■
L5-02: Fault@Reset Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-02
(049F)
Fault@Reset Select
Sets the function that sends signals to the MFDO terminal set for
Fault [H2-xx = 3]
while the
drive is automatically restarting.
1
(1, 2)
1 : Disable Fault Output
2 : Enable Fault Output
■
L5-04: Interval Reset Time
No.
(Hex.)
Name
Description
Default
(Range)
L5-04
(046C)
Interval Reset Time
Sets the time interval between each Auto Restart attempt. This function is enabled when
L5-05 =
2 [Reset Method = Use L5-04 Time]
.
10.0 s
(0.5 - 600.0 s)
■
L5-05: Reset Method
No.
(Hex.)
Name
Description
Default
(Range)
L5-05
(0467)
Reset Method
Sets the count method for the Auto Restart operation.
1
(1, 2)
1 : Continuous
Counts the number of successful fault resets through Auto Restart.
When this value >
L5-01
, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
2 : Use L5-04 Time
Counts the number of all fault resets (successful and unsuccessful) through Auto Restart. The drive repeats the
Auto Restart process in the intervals set in
L5-04 [Interval Reset Time]
.
When this value >
L5-01
, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
■
L5-07: OL1-4 Auto-Reset Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-07
(0B2A)
OL1-4 Auto-Reset Select
Use these 4 digits to set the Auto Restart function for
oL1
to
oL4
. From left to right, the digits set
oL1
,
oL2
,
oL3
, and
oL4
, in order.
1111
(0000 - 1111)
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...