SIEPCYEUOQ2V01A Q2V Technical Manual
663
■
L6-02: Trq Det1 Level
No.
(Hex.)
Name
Description
Default
(Range)
L6-02
(04A2)
Trq Det1 Level
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
•
Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
•
You can also use an analog input terminal to supply the torque detection level. To enable this function, set
H3-xx = E [MFAI Function
Select = OvUntrq Level]
. If you set
L6-02
and
H3-xx = E
, the analog input is most important and the drive disables
L6-02
.
■
L6-03: Trq Det1 Time
No.
(Hex.)
Name
Description
Default
(Range)
L6-03
(04A3)
Trq Det1 Time
Sets the detection time for Overtorque/Undertorque Detection 1.
0.1 s
(0.0 - 10.0 s)
■
L6-04: Trq Det2 Select
No.
(Hex.)
Name
Description
Default
(Range)
L6-04
(04A4)
Trq Det2 Select
Enables overtorque and undertorque detection and the operation of drives (operation status) after
detection.
0
(0, 1)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-05 [Trq Det2
Level]
for the length of time set in
L6-06 [Trq Det2 Time]
. The drive detects undertorque if the motor current or
output torque is less than the level set in
L6-05
for the length the time set in
L6-06
. Adjust the conditions using
parameters
L6-53, L6-54, and L6-55 [Trq Det2 Type, Trq Det2 Action, and Trq Det2 Condition]
.
0 : Disabled
1 : Enabled
■
L6-05: Trq Det2 Level
No.
(Hex.)
Name
Description
Default
(Range)
L6-05
(04A5)
Trq Det2 Level
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
Note:
Overtorque/Undertorque Detection 2 cannot set the detection level for the analog input terminal.
■
L6-06: Trq Det2 Time
No.
(Hex.)
Name
Description
Default
(Range)
L6-06
(04A6)
Trq Det2 Time
Sets the detection time for Overtorque/Undertorque Detection 2.
0.1 s
(0.0 - 10.0 s)
■
L6-07: Trq Detect Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
L6-07
(04E5)
Trq Detect Filter Time
Sets the time constant for a primary filter to the torque reference or to the output current used to
detect overtorque/undertorque.
0 ms
(0 - 1000 ms)
■
L6-08: MechF Enable
No.
(Hex.)
Name
Description
Default
(Range)
L6-08
(0468)
MechF Enable
Enables mechanical deterioration detection and how the drive operates (operation status) after
detection.
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...