SIEPCYEUOQ2V01A Q2V Technical Manual
667
■
L7-03: FW Reg. TrqLimit
No.
(Hex.)
Name
Description
Default
(Range)
L7-03
(04A9)
RUN
FW Reg. TrqLimit
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
•
The lower torque limit is enabled when you set the torque limit by the following method.
–
Set
H3-02 or H3-10 = 9, D [MFAI Function Select = FW Trq Lim, GenerTrqLim]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-04: RV Reg. TrqLimit
No.
(Hex.)
Name
Description
Default
(Range)
L7-04
(04AA)
RUN
RV Reg. TrqLimit
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
200%
(0 - 300%)
Note:
•
Use this method to set the torque limit and enable the lower torque limit:
–
Set
H3-02 or H3-10 = 9, D [MFAI Function Select = FW Trq Lim, GenerTrqLim]
.
–
Use a communication option to set the torque limits
•
You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect
oC
[Overcurrent]
.
•
If you set the value too low with large loads, the motor can stall.
■
L7-06: TrqLimit Integral Time
No.
(Hex.)
Name
Description
Default
(Range)
L7-06
(04AC)
TrqLimit Integral Time
Sets the integral time constant for the torque limit function.
200 ms
(5 - 10000 ms)
Decrease the setting value to increase torque limit responsiveness when you use torque limits and
L7-07 = 2
[TrqLimit@Acc/Decel = I-ctrl@Ac/Dec]
.
If there is hunting when torque limits are active, increase the setting value.
■
L7-07: TrqLimit@Acc/Decel
No.
(Hex.)
Name
Description
Default
(Range)
L7-07
(04C9)
TrqLimit@Acc/Decel
Sets the torque limit function during acceleration and deceleration.
1
(1, 2)
1 : P-ctrl@Ac/Dec
The torque limit function works with proportional control during acceleration and deceleration, and switches to
integral control at constant speed. Use this setting when quickly reaching the target speed is more important than
the torque limit during speed changes.
2 : I-ctrl@Ac/Dec
The torque limit function always uses integral control. Use this setting when a very accurate torque limit is
necessary during speed changes, for example in winding machine applications.
If you make the torque limit the most important, it can:
•
Increase the acceleration and deceleration times.
•
Not let the motor speed reach the frequency reference value during run at constant speed.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...