L7-16: TrqLimit@Start
No.
(Hex.)
Name
Description
Default
(Range)
L7-16
(044D)
TrqLimit@Start
Assigns a time filter to allow the torque limit to build at start.
1
(0, 1)
0 : Disabled
There is torque limit at start without a delay time.
Use this setting to maximize the response time when sudden acceleration or deceleration at start is necessary.
1 : Enabled
There is a delay time of 64 ms at start to build the torque limit.
◆
L8: DRIVE PROTECTION
L8 parameters
set protective functions that prevent faults such as overheating, phase loss, and ground faults.
■
L8-01: 3%ERF DBR Protection
No.
(Hex.)
Name
Description
Default
(Range)
L8-01
(04AD)
3%ERF DBR Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0
(0, 1)
0 : Disabled
Disables braking resistor protection. Use this setting for dynamic braking options that are not Yaskawa ERF series
braking resistors.
1 : Enabled
Enables protection for Yaskawa ERF series braking resistors.
Note:
Set
L8-01 = 1
and
H2-01 to H2-03 = 4C [MFDO Function Select = BrkRes Fault]
. Use a sequence to turn OFF power with MFDO.
■
L8-02: Overheat Alm Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-02
(04AE)
Overheat Alm Level
Sets the
oH
detection level in temperature.
Determined by o2-04, C6-
01
(50 - 150 °C)
If the heatsink temperature is more than the temperature set in this parameter, the drive detects an overheat pre-
alarm. To enable this function, set one of
H2-01 to H2-03 [MFDO Function Select]
to
4E [Drive PreOH]
.
If the temperature increases to the overheat fault level, the drive will trigger an
oH1 [Heatsink Overheat]
fault and
stop operation.
■
L8-03: Overheat Pre-Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets the operation of drives when an
oH
alarm is detected.
3
(0 - 4)
0 : Ramp->Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for
Fault [H2-01 to H2-03 =
3]
activates.
1 : Coast->Stop
The output turns off and the motor coasts to stop. The output terminal set for
Fault [H2-01 to H2-03 = 3]
activates.
2 : Fast Stop (C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. The output terminal set for
Fault
[H2-01 to H2-03 = 3]
activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...