674
SIEPCYEUOQ2V01A Q2V Technical Manual
•
With a regenerative converter, for example D1000.
•
With a regenerative unit, for example R1000.
•
When connecting braking resistor options to the drive, for example CDBR units.
•
Without an internal braking transistor.
1 : Enabled
Protects internal braking transistor when using a braking transistor or optional braking resistors.
■
L8-56: StallP@Acc Activation Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-56
(047D)
Expert
StallP@Acc Activation
Time
Sets the length time that the acceleration stall prevention function can continue to operate before
the drive detects an
STPo [Motor Step-Out Detected]
.
5000 ms
(100 - 5000 ms)
Note:
If this value is too small, it can cause incorrect detection of
STPo
. If this value is too large, the drive will not detect
STPo
.
■
L8-57: StallP Retry Counts
No.
(Hex.)
Name
Description
Default
(Range)
L8-57
(047E)
Expert
StallP Retry Counts
Sets the number of times the acceleration stall prevention function can operate until speeds agree
before the drive detects an
STPo [Motor Step-Out Detected]
.
10
(1 - 10 times)
Note:
If this value is too small, it can cause incorrect detection of
STPo
. If this value is too large, the drive will not detect
STPo
.
■
L8-90: STPo Detect Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-90
(0175)
Expert
STPo Detect Level
Sets the detection level that the control fault must be equal to or more than to cause an
STPo
[Motor Step-Out Detected]
.
Determined by A1-02
(0 - 5000 times)
This function detects when PM motors are not synchronized.
The drive cannot detect when motors are not synchronized because the frequency reference is low during start up
and the motor is locked. If fault detection is necessary in these conditions, set the control fault detection level to
enable detection of desynchronization because of motor locking. Increase the setting in 5-unit increments.
■
L8-93: Lso Detect Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-93
(073C)
Expert
Lso Detect Time
Sets the length of time the drive will wait to start baseblock after detecting
LSo [Low Speed Motor
Step-Out]
.
1.0 s
(0.0 - 10.0 s)
Set this parameter to 0.0 to disable the function.
■
L8-94: Lso Detect Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-94
(073D)
Expert
Lso Detect Level
Sets the detection level for
LSo [Low Speed Motor Step-Out]
as a percentage of
E1-04 [Max
Output Frequency]
.
3%
(0 - 10%)
■
L8-95: Lso Amount
No.
(Hex.)
Name
Description
Default
(Range)
L8-95
(077F)
Expert
Lso Amount
Sets the average count of
LSo [Low Speed Motor Step-Out]
detections.
10
(1 - 50 times)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...