696
SIEPCYEUOQ2V01A Q2V Technical Manual
Note:
•
Select the setting unit of these parameters:
–
d1-01 to d1-17 [Reference 1 to Jog Reference]
–
U1-01 [Frequency Reference]
–
U1-02 [Output Frequency]
–
U1-05 [Motor Speed]
–
U1-16 [SFS Output Frequency]
–
U4-14 [PeakHold OutFreq]
•
For monitor 2, the setting value is always
0 [0.01 Hz]
.
0 : 0.01 Hz
1 : 0.01% (100%=E1-04)
The maximum output frequency is 100%.
2 : rpm
The drive uses the maximum output frequency and number of motor poles calculate this value automatically.
Note:
When you set
o1-03 = 2 [r/min]
, make sure that you set the number of motor poles in these parameters:
•
E2-04 [Motor Pole Count]
•
E4-04 [M2 Pole Count]
•
E5-04 [PM Mot Pole Count]
•
E9-08 [Motor Pole Count]
3 : User-selected units
Uses
o1-10
and
o1-11
to set the unit of measure. The value of parameter
o1-10
is the value when you remove the
decimal point from the maximum output frequency. Parameter
o1-11
is to the number of digits after the decimal
point in the maximum output frequency.
To display a maximum output frequency of 100.00, set parameters to these values:
•
o1-10 = 10000
•
o1-11 = 2 [FrqDisplay Decimal Places = (XXX.XX) 2 Decimal Places]
■
o1-04: V/f Pattern Unit for Display
No.
(Hex.)
Name
Description
Default
(Range)
o1-04
(0503)
V/f Pattern Unit for Display
Sets the setting unit for parameters that set the V/f pattern frequency.
Determined by A1-02
(0, 1)
Note:
•
Select the units for these parameters:
–
E1-04 [Max Output Frequency]
–
E1-06 [Base Frequency]
–
E1-07 [Mid A Frequency]
–
E1-09 [Min Output Frequency]
–
E1-11 [Mid B Frequency]
–
E9-02 [Maximum Speed]
–
E9-04 [Base Frequency]
•
For motor 2, the settings are always
0 [Hz]
.
0 : Hz
1 : rpm
When you set
o1-04 = 1 [rpm]
, you must also use these parameters to set the motor pole count:
•
E2-04 [Motor Pole Count]
•
E5-04 [PM Mot Pole Count]
•
E9-08 [Motor Pole Count]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...