716
SIEPCYEUOQ2V01A Q2V Technical Manual
0 : Rotary Auto Tune
1 : Static1 AutoTune
2 : Static (R)
■
T1-02: Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
T1-02
(0702)
Motor Rated Power
Uses the units set in
o1-58 [Mot Capacity Unit]
to set the motor rated output power.
Determined by o2-04, C6-
01
(0.00 - 650.00 kW)
■
T1-03: Motor Rated Voltage
No.
(Hex.)
Name
Description
Default
(Range)
T1-03
(0703)
Motor Rated Voltage
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output motors.
Determined by o2-04, C6-
01
(200 V Class: 0.0 - 255.5 V,
400 V Class: 0.0 - 511.0 V)
If you do Auto-Tuning on a drive-dedicated motor or a specialized motor for vector control, the voltage or
frequency can be lower than that of a general-purpose motor. Always compare the data from the nameplate or test
report with the Auto-Tuning results and check for differences. Enter the voltage necessary to operate the motor in
no-load conditions at rated speed for better control precision around rated speed. If the motor test report or the
motor nameplate is not available, enter approximately 90% of the motor rated voltage.
If the drive input power supply voltage is low, enter approximately 90% of the input voltage. When the input
power supply voltage is low, the current will increase. Make sure that the main power supply capacity is correct
and use a molded-case circuit breaker for the drive.
■
T1-04: Motor Rated Current
No.
(Hex.)
Name
Description
Default
(Range)
T1-04
(0704)
Motor Rated Current
Sets the rated current (A) of the motor.
Determined by o2-04
(10% to 200% of the drive
rated current)
Set the motor rated current between 50% and 100% of the drive rated current for the best performance. Enter the
current at the motor base speed.
■
T1-05: Motor Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
T1-05
(0705)
Motor Base Frequency
Sets the base frequency (Hz) of the motor.
50.0 Hz
(0.0 - 590.0 Hz)
When Auto-Tuning is carried out, the value of
T1-05
is set to
E1-04 [Max Output Frequency]
. If
T1-05 < 40 Hz
,
E1-04
= 40 Hz. If you operate the drive at a speed that is higher than the base frequency, or if you operate in the
field weakening range, set
E1-04
(
E3-04
for motor 2) to the maximum output frequency after you complete Auto-
Tuning.
■
T1-06: Motor Poles Number
No.
(Hex.)
Name
Description
Default
(Range)
T1-06
(0706)
Motor Poles Number
Sets the number of motor poles.
4
(2 to 120)
■
T1-07: Motor Base Speed
No.
(Hex.)
Name
Description
Default
(Range)
T1-07
(0707)
Motor Base Speed
Sets the motor base speed for Auto-Tuning (min
-1
(r/min)).
1450 min
-1
(r/min)
(0 - 35400 min
-1
(r/min))
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...