SIEPCYEUOQ2V01A Q2V Technical Manual
717
■
T1-09: Motor NoLoad Current
No.
(Hex.)
Name
Description
Default
(Range)
T1-09
(0709)
Motor NoLoad Current
Sets the no-load current of the motor.
-
(0A - T1-04; max. of
2999.9)
Note:
The display units are different for different models:
•
0.01 A: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1 A: 2056 to 2082, 4031 to 4060
The value shown is the no-load current that the drive automatically calculates from the values set in
T1-02 [Motor
Rated Power]
and
T1-04 [Motor Rated Current]
. Set the no-load current shown on the motor test report. If the
motor test report is not available, do not change this parameter.
■
T1-10: Motor Rated Slip Frequency
No.
(Hex.)
Name
Description
Default
(Range)
T1-10
(070A)
Motor Rated Slip
Frequency
Sets motor rated slip.
-
(0.000 - 20.000 Hz)
Shows 0.000 Hz as the default value. Set the rated slip shown on the motor test report. If the motor test report is
not available, do not change this parameter.
■
T1-11: Motor Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
T1-11
(070B)
Motor Iron Loss
Sets the iron loss for calculating the energy-saving coefficient.
Determined by E2-11 or
E4-11
(0 - 65535 W)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the
E2-10 [Motor Iron Loss]
or
E4-10 [M2 Iron Loss]
for the motor output set in
T1-02
[Motor Rated Power]
. If the motor test report is available, enter the motor iron loss value to
T1-11
.
■
T1-12: Test Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
T1-12
(0BDB)
Test Mode Selection
Sets the function to enable Test Mode after Stationary Auto-Tuning. When you can operate the
motor with a light load attached after Stationary Auto-Tuning is complete, enable this parameter.
0
(0, 1)
0 : No
1 : Yes
After Auto-Tuning, the drive automatically sets
E2-02 [Mot Rated Slip]
and
E2-03 [Mot No-Load Current]
when
you operate the motor for the first time in Drive Mode.
Note:
After Auto-Tuning is complete and you set the drive to Drive Mode, operate the motor in these conditions:
•
Make sure that you connect all wiring between the drive and motor
•
Make sure that a mechanical brake on the motor shaft is not locked
•
Keep the motor-load ratio at 30%
•
Hold constant speed for longer than 1 second at a minimum of 30% of the speed set in
E1-06 [Base Frequency]
(the default setting is
the same as the maximum frequency).
■
T1-13: No-load Voltage
No.
(Hex.)
Name
Description
Default
(Range)
T1-13
(0BDC)
No-load Voltage
Sets the no-load voltage of the motor. When the no-load voltage at rated speed is available, for
example on the motor test report, set the voltage in this parameter. If the no-load voltage is not
available, do not change this parameter.
T1-03 × 0.9
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...