720
SIEPCYEUOQ2V01A Q2V Technical Manual
0 : mV/rpm
1 : mV/(rad/sec)
Note:
•
When
T2-13 = 0
, the drive will use
E5-24 [PM BackEMF L-L Vrms (mV/rpm)]
and will automatically set
E5-09 [PM BackEMF Vpeak
(mV/(rad/ s))] = 0.0
.
•
When
T2-13 = 1
, the drive will use
E5-09
and will automatically set
E5-24 = 0.0
.
■
T2-14: PMMot KE Voltage Constant
No.
(Hex.)
Name
Description
Default
(Range)
T2-14
(0737)
PMMot KE Voltage
Constant
Sets the motor induced voltage constant (Ke).
Determined by T2-13
(0.0 - 2000.0)
■
T2-15: PullInCurrLv@PM Motor Tuning
No.
(Hex.)
Name
Description
Default
(Range)
T2-15
(0756)
PullInCurrLv@PM Motor
Tuning
Sets the level of the pull-in current as a percentage of
E5-03 [PM Mot Rated Current (FLA)]
.
Usually it is not necessary to change this setting.
30%
(0 - 120%)
If the load inertia is high, increase the setting value.
◆
T3: ASR
■
T3-00: Control Loop Tune Selection
No.
(Hex.)
Name
Description
Default
(Range)
T3-00
(1198)
Control Loop Tune
Selection
Sets the type of Control Auto-Tuning.
2
(2, 3)
2 : Dec Rate Tuning
3 : KEB Tuning
◆
T4: SIMPLE VECTOR
Use
T4 parameters
to input the data necessary for motor parameter Auto-Tuning when
A1-02 = 8 [Control
Method = EZ Vector]
. Two modes are available.
T4-01
Setting
Operational overview
Items input for tuning
Items tuned
0
Follow the instructions in the setup
wizard on the keypad to manually
enter the necessary motor
parameters.
•
T4-02 [Motor Type Selection]
•
T4-03 [Motor Max Revolutions]
•
T4-04 [Motor Rated Revolutions]
•
T4-05 [Motor Rated Frequency]
•
T4-06 [Motor Rated Voltage]
•
T4-07 [Motor Rated Current]
•
T4-08 [Motor Rated Capacity]
•
T4-09 [Motor Poles Number]
•
E9-01 [Motor Type Selection]
•
E9-02 [Maximum Speed]
•
E9-03 [Rated Speed]
•
E9-04 [Base Frequency]
•
E9-05 [Base Voltage]
•
E9-06 [Motor Rated Current]
•
E9-07 [Motor Rated Power (kW)]
•
E9-08 [Motor Pole Count]
•
E9-09 [Motor Rated Slip]
•
E9-10 [Motor L-L Resistance]
1
Do only line-to-line resistance
tuning.
Motor Rated Current
E9-10 [Motor L-L Resistance]
*1
When you use a PM motor or a synchronous reluctance motor, it is not necessary to enter the rated frequency. The drive will use the
rated rotation speed and number of motor poles to automatically calculate the rated frequency.
■
T4-01: EZ Tune Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
T4-01
(3130)
EZ Tune Mode Selection
Sets the type of Auto-Tuning for EZOLV control.
0
(0, 1)
0 : Motor Constant
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...