SIEPCYEUOQ2V01A Q2V Technical Manual
93
3.14
Decrease Noise
Note:
The main circuit terminal block for the drive and the terminal block for the noise filter come in different shapes. Use caution when you
prepare the ends of the wires.
◆
Connect a Noise Filter to the Input Side (Primary Side)
High-speed switching makes noise in the drive output. This noise flows from the drive to the power supply, and
can possibly have an effect on other equipment. Install a noise filter to the input side of the drive to decrease the
quantity of noise that flows to the power supply. A noise filter also prevents noise from entering the drive from the
power supply.
•
Use a noise filter specially designed for drives.
•
Install the noise filter as close as possible to the drive.
A - Power supply
B - Input side (primary side) noise
filter
C - Drive
D - Other controller
Note:
The input side (primary side) noise filter model is LNFD-xx.
Figure 3.42 Example of Connecting the Noise Filter on the Input Side (Primary Side)
◆
Connect a Noise Filter to the Output Side (Secondary Side)
A noise filter on the output side of the drive decreases inductive noise and radio frequency interference.
NOTICE:
Do not connect phase-advancing capacitors, LC/RC noise filters, or leakage breakers (RCM/RCD) to the motor
circuit. If you connect these devices to the output circuits, it can cause damage to the drive and connected equipment.
A - Power supply
B - Drive
C - Noise filter on output side
(secondary side)
D - Motor
Figure 3.43 Example of Connecting the Noise Filter on the Output Side (Secondary Side)
Note:
Glossary
•
Radio frequency interference:
Electromagnetic waves radiated from the drive and cables make noise through the full radio bandwidth that can have an effect on
nearby devices.
•
Inductive noise:
The noise from electromagnetic induction can have an effect on the signal line and can cause the controller to malfunction.
■
Prevent Inductive Noise
In addition to installing a noise filter, you can also run all wiring through a grounded metal conduit to decrease
inductive noise occurring at the output side. Put the cables a minimum of 30 cm (11.8 in) away from the signal
line to prevent induced noise. Ground the cables to metal conduits.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...