3.15 Protect the Drive during Failures
SIEPCYEUOQ2V01A Q2V Technical Manual
95
3.15
Protect the Drive during Failures
◆
Factory-Recommended Branch Circuit Protection for UL Listing
Use branch circuit protection to protect against short circuits and to maintain compliance with UL61800-5-1. The
manufacturer recommends connecting semiconductor protection fuses on the input side for branch circuit
protection. Refer to
Three-Phase 400 V Class on page 96
,
Single-Phase 200 V Class on page 95
, and
for more information.
WARNING!
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the drive
or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators
are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of
the problem, contact the manufacturer before you energize the drive or peripheral devices. If you do not fix the problem before
you operate the drive or peripheral devices, it can cause serious injury or death.
•
200 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
31,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
•
400 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
31,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I
(CEC), and local codes.
◆
Three-Phase 200 V Class
Table 3.20 Factory-Recommended Branch Circuit Protection: Three-Phase 200 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, CC, and T Fuse
Rated Current
A
Model
Input Rated Current
A
2001
0.18 (1/6)
0.1 (1/6)
3
FWH-25A14F
25
2002
0.37 (1/4)
0.25 (1/4)
6
FWH-25A14F
25
2004
0.75 (3/4)
0.55 (1/2)
6
FWH-25A14F
25
2006
1.1 (1.5)
0.75 (1)
10
FWH-25A14F
25
2008
1.5 (2)
1.1 (1.5)
15
FWH-70B
70
2010
2.2 (3)
1.5 (2)
20
FWH-70B
70
2012
3.0 (4)
2.2 (3)
25
FWH-70B
70
2018
3.7 (5)
3.0 (4)
30
FWH-90B
90
2021
5.5 (5)
4.0 (5)
40
FWH-90B
90
2030
7.5 (10)
5.5 (7.5)
-
FWH-100B
100
2042
11 (15)
7.5 (10)
-
FWH-150B
150
2056
15 (20)
11 (15)
-
FWH-200B
200
2070
18.5 (25)
15 (20)
-
FWH-200B
200
2082
22 (30)
18.5 (25)
-
FWH-225A
225
◆
Single-Phase 200 V Class
Table 3.21 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, T, and CC Fuse
Rated Current
A
Model
Input Rated Current
A
B001
0.18 (1/6)
0.1 (1/6)
3
FWH-25A14F
25
B002
0.37 (1/4)
0.25 (1/4)
6
FWH-25A14F
25
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...