Auto-Tuning
Auto-Tuning uses motor characteristics to automatically set drive parameters for vector control. Think about the
type of motor, drive control method, and the motor installation environment and select the best Auto-Tuning
method.
WARNING!
Crush Hazard. Rotational Auto-Tuning rotates the motor at 50% or more of the motor rated frequency. Make sure
that there are no issues related to safety in the area around the drive and motor. Increased motor frequency can cause serious
injury or death.
◆
Auto-Tuning for Induction Motors
This section gives information about Auto-Tuning for induction motors. Set motor parameters
E1-xx and E2-xx
(or, for motor 2,
E3-xx and E4-xx
) for Auto-Tuning.
Note:
Do Stationary Auto-Tuning if you cannot do Rotational Auto-Tuning. There can be large differences between the measured results and
the motor characteristics when Auto-Tuning is complete. Examine the parameters for the measured motor characteristics after you do
Stationary Auto-Tuning.
Table 4.7 Auto-Tuning Mode Selection
Method
Parameter
Settings
Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
V/f Control
(0)
OLVector
(2)
Rotational Auto-
Tuning
T1-01 = 0
•
When you can decouple the motor and load the motor can rotate freely while Auto-
Tuning.
•
When operating motors that have fixed output characteristics.
•
When it is necessary to use motors that have high-precision control.
•
When you cannot decouple the motor and load, but the motor load is less than 30%.
x
x
Stationary Auto-Tuning
1
T1-01 = 1
•
When you cannot decouple the motor and load.
•
When the motor load is more than 30%.
•
When the information from the motor test report or motor nameplate is not available.
With Stationary Auto-Tuning, the energized drive stays stopped for approximately 1
minute. During this time, the drive automatically measures the necessary motor
parameters.
•
When operating the motor with a less than 30% light load after Auto-Tuning.
Set
T1-12 = 1 [Test Mode Selection = Yes]
to do a test run after Auto-Tuning.
-
x
Stationary Line-Line
Resistance
T1-01 = 2
•
After Auto-Tuning, the wiring distance between the drive and motor changed by 50 m
or more.
•
When the wiring distance is 50 m or more in the V/f Control mode.
•
When the motor output and drive capacity are different.
x
x
■
Input Data for Induction Motor Auto-Tuning
To do Auto-Tuning, input data for the items that have an "x" in the table below. Before starting Auto-Tuning,
prepare the motor test report or record the information on the motor nameplate as a reference.
Table 4.8 Input Data for Induction Motor Auto-Tuning
Input Data
Parameter
Unit
Auto-Tuning Mode
(T1-01 Setting)
Rotational Auto-Tuning
(0)
Stationary Auto-Tuning
1
(1)
Stationary Line-Line
Resistance
(2)
Motor Rated Power
T1-02
kW
x
x
x
Motor Rated Voltage
T1-03
V
x
x
-
Motor Rated Current
T1-04
A
x
x
x
Motor Base Frequency
T1-05
Hz
x
x
-
Motor Poles Number
T1-06
-
x
x
-
Motor Base Speed
T1-07
min
-1
x
x
-
Motor NoLoad Current
T1-09
A
-
x
-
Motor Rated Slip
Frequency
T1-10
Hz
-
x
-
Motor Iron Loss
T1-11
W
x
-
-
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...