Make sure that the motor is fully stopped.
•
Connect the motor with the machine.
Make sure that there are no loose installation screws and that the motor load shafts and machine junctions are
correctly secured.
•
Keep the keypad near you to push
immediately if there is unusual or incorrect operation.
■
Items to Check before Operation
•
Make sure that the direction of the machine operation is correct (The motor must rotate in the correct direction).
•
Make sure that the motor accelerates and decelerates smoothly.
◆
Do an Actual-Load Test Run
Before a test run, make sure that
U1-03 [Output Current]
is not too high.
Connect the motor and machine, then do the test run with the same procedure that you used for the no-load test
run.
1.
Energize the drive, or push
to show the frequency reference screen.
2.
Use
/
/
/
to set
d1-01 = 6.00 [Reference 1 = 6.00 Hz]
, then push
.
3.
Push
to illuminate the LOCAL/REMOTE LED.
4.
Push
.
The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.
5.
Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.
If the drive detects a fault, remove the cause.
6.
Push
to increase the frequency reference value.
Change the setting value in increments of 10 Hz if necessary and examine the response.
Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
7.
Each time you increase the setting value, use
U1-03 [Output Current]
to check the drive output current.
When the output current of the drive is not more than the motor rated current, the status is correct.
8.
Make sure that the motor rotates correctly, then push
.
The RUN LED flashes and goes off when the motor stops completely.
9.
Change the frequency reference and direction of motor rotation, and make sure that there are no unusual
sounds or vibrations.
10.
If the control function causes hunting or oscillation errors, adjust the settings to stop the errors.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...