224
SIEPCYEUOQ2V01A Q2V Technical Manual
Code
Name
Causes
Possible Solutions
CPF00, CPF01,
CPF02, CPF03,
CPF06, CPF08,
CPF11 to
CPF14, CPF16
to CPF24,
CPF38
Control Circuit Error
A drive hardware problem occurred.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact the
manufacturer or your nearest sales representative.
Note:
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for these faults.
Code
Name
Causes
Possible Solutions
CPF06
EEPROM Memory Data Error
The drive power supply was de-energized while a
communication option card entered a parameter
Write command.
Set
A1-03 = 2220, 3330 [Init Parameters = 2-Wire Initialization,
3-Wire Initialization]
and initialize the drive.
An EEPROM peripheral circuit error occurred.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact the
manufacturer or your nearest sales representative.
Note:
•
The drive detects this error if there is an error in the data written to the EEPROM of the drive.
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for this fault.
Code
Name
Causes
Possible Solutions
CPF25
Terminal Board not Connected
The terminal board is not correctly connected to the
drive.
1.
De-energize the drive.
2.
Correctly connect the terminal board to the drive.
3.
Re-energize the drive.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dCE1
Communication Error1
A drive hardware problem occurred temporarily due
to noise.
•
Remove the cause of the noise.
•
If the fault stays, replace the control board or the drive.
Note:
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for these faults.
Code
Name
Causes
Possible Solutions
dCE2
Communication Error2
A drive hardware problem occurred temporarily due
to noise.
•
Remove the cause of the noise.
•
If the fault stays, replace the control board or the drive.
Note:
•
Do a Fault Reset to clear the fault.
•
Fault trace is not available for these faults.
Code
Name
Causes
Possible Solutions
dEv
Speed Deviation
The load is too heavy.
Decrease the load.
Acceleration and deceleration times are set too
short.
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Time]
.
The
dEv
detection level settings are incorrect.
Adjust
F1-10 [Speed Dev Level]
and
F1-11 [Speed Dev Delay
Time]
.
The load is locked up.
Examine the machine.
The holding brake is stopping the motor.
Release the holding brake.
Note:
•
The drive detects this error if the difference between the detected speed and the speed reference is more than the setting of
F1-10
for longer than
F1-11
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, the drive will operate the motor as specified by the stopping method set in
F1-04 [Speed Dev Detection Select]
.
Code
Name
Causes
Possible Solutions
dv7
Polarity Judge Timeout
There is a disconnection in the motor coil winding.
Measure the motor line-to-line resistance and replace the motor if
a coil is disconnected.
The screws on the drive output terminals are loose.
Tighten the terminal screws to the correct tightening torque.
Note:
•
The drive detects this error if it cannot detect polarity in a pre-set length of time.
•
Do a Fault Reset to clear the fault.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...