SIEPCYEUOQ2V01A Q2V Technical Manual
483
When the drive accelerates to the output frequency set in
b6-01
, it holds that frequency for the time set in
b6-02
[Dwell Time@Start]
, and starts to accelerate again.
■
b6-02: Dwell Time@Start
No.
(Hex.)
Name
Description
Default
(Range)
b6-02
(01B7)
Dwell Time@Start
Sets the length of time that the drive will hold the output frequency when the motor starts.
0.0 s
(0.0 - 10.0 s)
■
b6-03: Dwell Ref@Stop
No.
(Hex.)
Name
Description
Default
(Range)
b6-03
(01B8)
Dwell Ref@Stop
Sets the output frequency that the drive will hold momentarily when ramping to stop the motor.
0.0
(Determined by A1-02)
When the drive decelerates to the output frequency set in
b6-03
, it holds that frequency for the time set in
b6-04
[Dwell Time@Stop]
and starts to decelerate again.
■
b6-04: Dwell Time@Stop
No.
(Hex.)
Name
Description
Default
(Range)
b6-04
(01B9)
Dwell Time@Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop the motor.
0.0 s
(0.0 - 10.0 s)
◆
b8: ENERGY SAVING
Energy-saving control improves overall system operating efficiency by operating the motor at its most efficient
level.
Set
b8-01
and these parameters according to the control method and the motor.
•
When you use V/f Control, set parameters
b8-04 to b8-06
.
•
When you use vector control with an induction motor, set parameters
b8-02 and b8-03
.
•
When you use a PM motor, set parameters
b8-16 and b8-17
.
Note:
•
Energy-saving control is not appropriate for applications with sudden changes in the load, or applications driving heavy loads such as a
traverse car application.
•
Energy-saving control maximizes operation based on precise motor data set to the drive. Make sure that you do Auto-Tuning and enter
the correct information about the motor before you use the Energy-saving control.
■
b8-01: eSave Ctrl Selection
No.
(Hex.)
Name
Description
Default
(Range)
b8-01
(01CC)
eSave Ctrl Selection
Sets the Energy-saving control function.
0
(0 - 2)
0 : Disabled
1 : Enabled
2 : Search Enabled
Note:
When
A1-02 = 6 [Control Method = PM AOLVector]
, you can only select setting
2
in Expert Mode.
■
b8-02: eSave Ctrl Gain
No.
(Hex.)
Name
Description
Default
(Range)
b8-02
(01CD)
RUN
Expert
eSave Ctrl Gain
Sets the gain for Energy-saving control.
Determined by A1-02
(0.0 - 10.0)
Increase the setting value to increase energy saving. If the setting value is too large, the motor will stall.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...