502
SIEPCYEUOQ2V01A Q2V Technical Manual
■
C5-01: ASR PGain 1
No.
(Hex.)
Name
Description
Default
(Range)
C5-01
(021B)
RUN
ASR PGain 1
Sets the gain to adjust ASR response.
Determined by A1-02
(0.00 - 300.00)
A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain will
cause vibration.
Note:
•
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train Function = PG Feedback]
to enable this parameter.
•
The drive usually sets Motor 1 ASR with
C5-01
and
C5-02 [ASR ITime 1]
. When you set
H1-xx = 45 [MFDI Function Select = ASR
Gain Switch]
, you can switch between
C5-01
and
C5-03 [ASR PGain 2]
. You can also use
C5-01
as an alternative to
C5-03
and
C5-02
as an alternative to
C5-04
when the speed is less than or equal to the frequency set in
C5-07 [ASR Gain Switch Frequency]
.
•
The drive automatically adjusts
C5-01
in ASR Tuning.
■
C5-02: ASR ITime 1
No.
(Hex.)
Name
Description
Default
(Range)
C5-02
(021C)
RUN
ASR ITime 1
Sets the ASR integral time.
Determined by A1-02
(0.000 - 60.000 s)
When you increase the integral time, the responsiveness will decrease. An integral time that is too short can cause
oscillation.
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train Function = PG Feedback]
to enable this parameter.
■
C5-03: ASR PGain 2
No.
(Hex.)
Name
Description
Default
(Range)
C5-03
(021D)
RUN
ASR PGain 2
Sets the gain to adjust ASR response.
Determined by A1-02
(0.00 - 300.00)
A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain will
cause vibration.
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train Function = PG Feedback]
to enable this parameter.
■
C5-04: ASR ITime 2
No.
(Hex.)
Name
Description
Default
(Range)
C5-04
(021E)
RUN
ASR ITime 2
Sets the ASR integral time.
Determined by A1-02
(0.000 - 60.000 s)
When you increase the integral time, the responsiveness will decrease. An integral time that is too short can cause
oscillation.
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train Function = PG Feedback]
to enable this parameter.
■
C5-05: ASR Limit
No.
(Hex.)
Name
Description
Default
(Range)
C5-05
(021F)
ASR Limit
Sets the ASR output limit where
E1-04 [Max Output Frequency]
is 100%.
5.0%
(0.0 - 20.0%)
If the motor rated slip is high, it is necessary to increase the setting for correct motor speed control. Use
U6-04
[ASR Output]
to make sure that ASR is operating at the limit set in this parameter. When ASR is operating at the
limit, correctly set the encoder (PG) signal before you make changes to
C5-05
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...