606
SIEPCYEUOQ2V01A Q2V Technical Manual
Note:
The drive compares the monitors set with
H2-26
as absolute values.
■
3E: PID Fbk Low
Setting Value
Function
Description
3E
PID Fbk Low
The terminal activates when the drive detects
FbL [PID Feedback Loss]
.
The drive detects
FbL [PID Feedback Loss]
when the PID feedback value <
b5-13 [Fdback Loss Lvl]
for longer
than the time set in
b5-14 [Fdback Loss Time]
.
Note:
Refer to
“
PID Feedback Loss Detection
”
for more information.
■
3F: PID Fbk High
Setting Value
Function
Description
3F
PID Fbk High
The terminal activates when the drive detects
FbH [Excessive PID Feedback]
.
The drive detects
FbH [Excessive PID Feedback]
when the PID feedback value >
b5-36 [PID HiHi Limit Level]
for longer than the time set in
b5-37 [PID HiHi Time]
.
Note:
Refer to
“
PID Feedback Loss Detection
”
for more information.
■
4A: DC Bus Undervolt
Setting Value
Function
Description
4A
DC Bus Undervolt
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with
L2-05 [UV
Detection Lvl (Uv1)]
. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of
L2-05
.
OFF : The DC bus voltage is more than the setting value of
L2-05
.
■
4B: FreqRef Loss
Setting Value
Function
Description
4B
FreqRef Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to
“
L4-05: FrefLoss Det.Selection on page 656
”
for more information.
■
4C: BrkRes Fault
Setting Value
Function
Description
4C
BrkRes Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
■
4D: Motor OL1
Setting Value
Function
Description
4D
Motor OL1
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of
90% of the detection level.
Note:
Refer to
“
L1-01: Motor Cool Type for OL1 Calc on page 631
”
for more information.
■
4E: Drive PreOH
Setting Value
Function
Description
4E
Drive PreOH
The terminal activates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alm Level]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...