SIEPCYEUOQ2V01A Q2V Technical Manual
661
Table 12.53 Overtorque/Undertorque Detection Parameters
Configuration Parameter
Overtorque/Undertorque Detection 1
Overtorque/Undertorque Detection 2
MFDO Function Select
•
Terminal NO-CM
•
Terminal DO1-O1C
•
Terminal DO2-O2C
H2-01, H2-02, and H2-03 = 32
N.O.: Activated when detected
H2-01, H2-02, and H2-03 = 37
N.O.: Activated when detected
H2-01, H2-02, and H2-03 = 33
N.C.: Disactivated when detected
H2-01, H2-02, and H2-03 = 38
N.C.: Disactivated when detected
Detection conditions and selection of operation after
detection
L6-01
L6-04
Detection Level
L6-02
L6-05
Analog Input Terminal
H3-xx = E
-
Detection Time
L6-03
L6-06
*1
You can also use an analog input terminal to supply the torque detection level. To enable this function, set
H3-xx = E [MFAI
Function Select = OvUntrq Level]
. If both
L6-02
and
H3-xx = E
are set, the analog input has priority and the setting of
L6-02
is
disabled.
You cannot use Overtorque/Undertorque Detection 2 to set the detection level for the analog input terminals.
Note:
In V/f Control, the drive uses the current level (100% of the drive rated output current) to detect overtorque/undertorque. In vector
control, the drive uses the motor torque (100% of the motor rated torque)to detect overtorque/undertorque. When you enable the
mechanical weakening detection function, the overtorque/undertorque detection level for all control modes is the current level (100% of
the drive rated output current).
■
Time Chart for Detection of Overtorque/Undertorque
Overtorque Detection Time Chart
When you use Overtorque/Undertorque Detection 1, the drive detects overtorque if the motor current or motor
torque is at the detection level set in
L6-02 [Trq Det1 Level]
for the time set in
L6-03 [Trq Det1 Time]
. Parameter
L6-01 [Trq Det1 Select]
sets the operation after detection.
When you use Overtorque/Undertorque Detection 2, set
L6-04 [Trq Det2 Select]
,
L6-05 [Trq Det2 Level]
, and
L6-
06 [Trq Det2 Time]
.
Set the terminal that outputs the alarm in
H2-01 to H2-03 [MFDO Function Select]
.
Figure 12.125 Overtorque Detection Time Chart
Note:
The drive applies a hysteresis of approximately 10% of the drive rated output current or the motor rated torque to the overtorque/
undertorque detection function.
Undertorque Detection Time Chart
When you use Overtorque/Undertorque Detection 1, the drive detects undertorque if the motor current or motor
torque is less than or equal to the detection level set in
L6-02
for the time set in
L6-03
. Parameter
L6-01
sets the
operation after detection.
When you use Overtorque/Undertorque Detection 2, set the operation in
L6-04, L6-05, and L6-06
.
Set the terminal that outputs an alarm in
H2-01 to H2-03
.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...