670
SIEPCYEUOQ2V01A Q2V Technical Manual
0 : Disabled
1 : 1PH Loss Det
If the drive loses one output phase, it will trigger
LF [Output Phase Loss]
.
The output turns off and the motor coasts to stop.
2 : 2/3PH Loss Det
If the drive loses more than one output phase, it will trigger
LF [Output Phase Loss]
.
The output turns off and the motor coasts to stop.
■
L8-09: Ground Fault Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-09
(04B5)
Ground Fault Selection
Sets the function to enable and disable ground fault protection.
Determined by o2-04
(0, 1)
0 : Disabled
The drive will not detect ground faults.
1 : Enabled
If there is high leakage current or a ground short circuit in one or two output phases, the drive will detect
GF
[Ground Fault]
.
Note:
If the ground path impedance is low,
oC [Overcurrent]
,
SC [Out Short Circuit or IGBT Fault]
, or
ov [DC Bus Overvoltage]
can stop the
motor.
■
L8-10: Fan Operate Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-10
(04B6)
Fan Operate Selection
Sets operation of the heatsink cooling fan.
1
(1 - 3)
1 : Dur Run (OffDly)
The drive turns on the fan when a Run command is active.
2 : Always On
The fan turns on when you supply power to the drive. When you release the Run command and the delay time set
in
L8-11 [Fan Off-Delay Time]
is expired, the fan stops. his setting extends the fan lifetime.
3 : Fan ON @Heating of Drive
The fan turns on when the drive detects that the main circuit is overheating.
■
L8-11: Fan Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-11
(04B7)
Fan Off-Delay Time
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the
Run command when
L8-10 = 1 [Fan Operate Selection = Dur Run (OffDly)]
.
60 s
(0 - 300 s)
■
L8-12: Ambient Temperature Setting
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +60 °C)
Note:
The setting range changes when the
L8-35 [Installation Selection]
value changes:
•
0 [IP00/IP20/Open-Chassis]
: -10 °C to +60 °C
•
1 [Side-by-Side Mounting]
: -10 °C to +50 °C
•
2 [UL Type 1]
: -10 °C to +50 °C
•
3 [Ext. Heatsink]
: -10 °C to +50 °C
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...