Adjust this parameter in these conditions:
•
When
n1-01 = 1, 2 [HuntPrev Selection = Enabled, Enabled (High Carrier)]
, if oscillation occurs when you
operate a motor with a light load, increase the setting value in 0.1-unit increments.
•
When
n1-01 = 1, 2
, if the motor stalls, decrease the setting value in 0.1-unit increments.
■
n1-13: DCBus Stab.Control
No.
(Hex.)
Name
Description
Default
(Range)
n1-13
(1B59)
Expert
DCBus Stab.Control
Sets the oscillation suppression function for the DC bus voltage.
0
(0, 1)
0 : Disabled
1 : Enabled
Note:
If the DC bus voltage does not become stable with light loads and the drive detects
ov [Overvoltage]
, set this parameter to 1.
■
n1-14: DCBus Stab Time
No.
(Hex.)
Name
Description
Default
(Range)
n1-14
(1B5A)
Expert
DCBus Stab Time
Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage. Set
n1-
13 = 1 [DCBus Stab.Control = Enabled]
to enable this parameter.
100.0 ms
(50.0 - 500.0 ms)
Note:
Adjust this parameter in 100 ms increments.
◆
n2: AFR - AUTO FREQ REGULATION
The speed feedback detection reduction function (or AFR: Automatic Frequency Regulator) helps the speed
become stable when you suddenly apply or remove a load.
Note:
Before you change
n2-xx parameters
, do one of these procedures:
•
Set the motor parameters and V/f pattern correctly.
•
Do Rotational Auto-Tuning.
■
n2-01: AFR Gain
No.
(Hex.)
Name
Description
Default
(Range)
n2-01
(0584)
AFR Gain
Sets the gain of the AFR function as a magnification value. Usually it is not necessary to change
this setting.
1.00
(0.00 - 10.00)
Adjust this parameter in these conditions:
•
If hunting or oscillation occurs with light loads, increase the setting value in 0.05-unit increments and examine
the response.
•
When torque is not sufficient with heavy loads or to make the torque or speed response better, decrease the
setting value in 0.05-unit increments and examine the response.
■
n2-02: AFR Time 1
No.
(Hex.)
Name
Description
Default
(Range)
n2-02
(0585)
AFR Time 1
Sets the time constant that sets the rate of change for the AFR function. Usually it is not necessary
to change this setting.
50 ms
(0 - 2000 ms)
Adjust this parameter in these conditions:
•
If there is hunting or oscillation with a light load, increase the setting value in 50 ms increments and examine
the response. If the load inertia is large, increase the setting value in 50 ms increments and examine the
response.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...