2 Design
2 - 70
High-function General-purpose Inverter RX2 Series User’s Manual
Pullout Method
1
Push the gray colored part on the PG Option Unit terminal block with a flathead screwdriver (2.5
mm widths or narrower), and the aperture for wire-inserting will open.
2
While you are holding the screwdriver in the hole, pull out the wire or pin-terminal.
3
Pull out the screwdriver.
Method of Disconnecting the Connector
1
Pull down the lock lever to the direction indicated by the arrow to release the lock.
2
Pull out the connector.
The encoder input terminal ((EAP/EAN/EBP/EBN/EZP/EZN) has a function to detect disconnection
when the wires are not connected. When you do not connect any encoders
(EAP/EAN/EBP/EBN/EZP/EZN not connected), turn the DIP switch 1 and 2 to OFF in order to disable
the disconnection function.
As for the encoder without Z-phase, turn the DIP switch 2 to OFF to disable the detection of Z-phase
disconnection.
PG Option Unit Disconnection Detection
Push the gray colored
part with your flathead
screwdriver.
Pull out the wire.
Pull out the screw driver.
Pull down the
lock lever.
Pull out the
connector.
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......