2 - 77
2 Design
High-function General-purpose Inverter RX2 Series User’s Manual
2-3 W
irin
g
2
2-
3-1
1 Compatibility C
onditions of UL
/CSA
Stand
ards
The condition in the next section UL standard explain the condition of the electrical safety. It is neces-
sary to comply with the description items such as temperature condition, installation condition etc.
UL CAUTION
GENERAL:
Model 3G3RX2 series inverter is an open type AC Inverter with three phase input and three phase out-
put. It is intended to be used in an enclosure. It is used to provide both an adjustable voltage and
adjustable frequency to the ac motor. The inverter automatically maintains the required volts-Hz ratio
allowing the capability through the motor speed range. It is a multi-rated device and the ratings are
selectable according to load types by operator with key pad operation.
3G3RX2 Series Models Short Circuit Rating and Overcurrent Protection
Device Rating
• 3G3RX2-A2
series models
Suitable for use on a circuit capable of delivering not more than (a) rms symmetrical amperes, at
(b) V maximum. (see table below)
• 3G3RX2-A4
3G3RX2-B4
series models
Suitable for use on a circuit capable of delivering not more than (a) rms symmetrical amperes, at
(b) V maximum. (see table below)
Conditions of Electrical Safety (LVD)
2-3-11 Compatibility Conditions of UL/CSA Standards
Standards
US
UL61800-5-1
CA
CSA 22.2 No.274
FS
IEC61800-5-2:2016 STO SIL3
ISO13849-1:2015 Cat.4 PLe
Markings:
Maximum Surrounding Temperature:
ND (Normal Duty):
50°C
LD (Low Duty):
50°C
*1
*1. For actual use, use within the temperature range indicated in the common specifications.
VLD (Very Low Duty):
45°C
*1
Storage Environment rating:
65°C (for transportation)
Instruction for installation:
pollution degree 2 environment and Over voltage category III
Electrical Connections:
See [Main circuit Wiring Diagram] of this Instruction Manual
Interconnection and wiring diagrams:
See [Outline of control circuit] of this Instruction Manual
3G3RX2-
(a)
(b)
200V
A2004 to A2220
5,000A rms
240V
A2300 to A2550
10,000A rms
240V
400V
A4007 to A4220
5,000A rms
500V
A4300 to A4550,B4750, B4900
10,000A rms
500V
B411K, B413K
18,000A rms
500V
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......