5 - 11
5 Monitor
High-function General-purpose Inverter RX2 Series User’s Manual
5
-5 P-N
V
oltage Mo
n
ito
r
5
5-5
P-N Voltage Monitor
Displays P-N voltage charged in the main circuit capacitor of an inverter.
Precautions for Correct Use
P-N voltage is DC voltage. The overvoltage error [E007] is generated in the following cases:
• When P-N voltage is over around 405 VDC in the class of 200 V inverter.
• When P-N voltage is over around 810 VDC in the class of 400 V inverter.
Parameter
Item
Parameter
Data
Description
DC voltage monitor
[dA-40]
0.0 to 1000.0 (V)
Displays the P-N voltage of inverter.