5 Monitor
5 - 16
High-function General-purpose Inverter RX2 Series User’s Manual
The output power monitor [dA-34] displays the current power output to the inverter.
The integrated output power monitor [dA-36] displays the integrated data of the power output to the
inverter.
Additional Information
• Display gain for Accumulation output power monitor [UA-15] mode, the displayed contents
can be converted with gain.
Value indicated on [dA-36] = “Calculated output power value (kWh)”/[UA-15]
([UA-15] can be set from 1. to 1000. by an unit.)
• Accumulation output power monitor clear [UA-14] to “01” and then determining it, you can
clear an integrated output power value.
• Also, if 40 (OKHC: clearing of integrated output power) has been assigned to one of the input
terminals, integrated input power value can be cleared via that terminal.
Parameter
5-8-2
Output Power Monitor
Item
Parameter
Data
Description
Output power monitor
[dA-34]
0.00 to 600.00 (kW)
Displays the output power.
Integrated output power
monitor
[dA-36]
0.0 to 100000.0 (kWh)
Displays the integrated value of output
power.
Accumulation output
power monitor clear
[UA-14]
00
Disable
01
Clear
Display gain for
Accumulation output
power monitor
[UA-15]
1 to 1000
Displays a value obtained by multiply-
ing by gain.
Input terminal function
[CA-01] to
[CA-11]
040
[OKHC] Clearing of integrated output
power terminal
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......