6 - 5
6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-1 B
asic Parame
ter Sett
ing
s
6
6-1-2 Invert
er Initia
lization
When the Initialize Mode selection [Ub-01] is chosen and [Ub-05] Initialize Enable is set to 01, the des-
ignated data can be initialized to the default data.
When you use an inverter of 3G3RX2 at the first time or you newly set the inverter, set Initialize Mode
selection [Ub-01] to 04 (Trip h para DriveProgramming) in order to complete the initial-
ization.
Only the trip history can be cleared without initialization of the stored parameter values.
Initial values to be stored after the initialization can be changed by changing the initial value selection
[Ub-02].
Precautions for Correct Use
• The following data cannot be initialized: DriveProgramming user parameter U00 to U63
(UE-10 to UE-73) setting value, cumulative operating hours monitor during RUN (dC-22),
cumulative power-ON time (dC-24), initialized data selection (Ub-02), duty type selection
(Ub-03), analog adjustment (Cb-30 to Cb-35), thermistor adjustment (Cb-41).
• The initialization sets the parameters to initial values. When the data before the initialization
is required, read out it with R/W function (Read) in LCD operator, or use CX-Drive to store it
in PC.
• The initialized parameters are not displayed, depends on Display restriction selection
(UA-10). Change the data to 00: total view to complete the initialization.
• When the soft lock selection (UA-16) setting bans on a change of parameter values, data
can not be initialized. Be sure to reset the ban on a change of parameter values to carry out
the initialization.
• When you select the data 01 in Initialize Enable (Ub-05) and press F2 key, the initialization
starts. Take a caution you can not undo the data once the initialization starts.
• Initialization cannot be initialized in the following states:
• During operation
• When the trip occurs
• During soft lock
• Even when the operation command is input during initialization, the inverter ignores the com-
mand. Input the operation command again after the initialization is finished.
6-1-2
Inverter Initialization
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......