6 - 9
6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-
2 Paramet
er Sett
ing f
o
r Mo
tor R
elated
6
6-
2-1 Motor
Basic Settin
gs
Precautions for Correct Use
• The motor could burn if the base frequency is set lower than the motor frequency. (Lower
than 50 Hz in case of standard induction motor)
• For setting the maximum frequency higher than 60 Hz, make sure the motor’s maximum
allowable frequency.
• The motor could burn if the maximum frequency and rated voltage are set to exceed the
specified range of rated voltage.
• After initialization, the motor protection function needs to be configured again. Otherwise, the
motor could burn.
Parameters for Synchronous Motor (SM)/ Permanent Magnetic
Motor (PMM)
Items of SM and
PMM motor
Parameters of inverter
Setting range
(unit)
Description
Default data
Capacity
[Hd102]
Async.Motor
capacity setting,
1st-motor
0.01 to 160.00
(kW)
Sets the motor capacity.
Varies
depending
on inverter
models and
settings of
duty rating.
Number of poles
[Hd103]
Async.Motor poles
setting, 1st-motor
2 to 48 (poles)
Sets the number of poles.
Varies
depending
on inverter
models and
settings of
duty rating.
Frequency
[Hd104]
Async.Motor Base
frequency setting,
1st-motor
10.00 to 590.00
(Hz)
Sets the base frequency
of motor.
Varies
depending
on inverter
models and
settings of
duty rating.
[Hd105]
Async.Motor Maxi-
mum frequency
setting, 1st-motor
10.00 to 590.00
(Hz)
Sets the max. frequency
of motor.
Varies
depending
on inverter
models and
settings of
duty rating.
Voltage
[Hd106]
Async.Motor rated
voltage, 1st-motor
1 to 1000 (V)
Sets the rated voltage of
motor.
200 V: 230
*1
400 V: 400
*1
Current
[Hd108]
Async.Motor rated
current, 1st-motor
0.01 to 10000.00
(A)
Sets the rated current of
motor.
Varies
depending
on inverter
models and
settings of
duty rating.
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......