6 Basic Parameter Settings
6 - 28
High-function General-purpose Inverter RX2 Series User’s Manual
First, the voltage SW and current SW are switched when the wiring is made.
Next, a command destination for the parameter [AA101] is set.
Parameter
RS485 communication is used to give a frequency command.
Precautions for Correct Use
For details, see
9-1 Communication Specifications
Parameter
Frequency command is given with a pulse string input.
Note To give a pulse string input, there are two methods. One is to use the main body’s terminals and the other is
to use the PG option unit.
Item
Parameters
Data
Description
Default
data
Main speed input
source selection,
1st-motor
[AA101]
01
Input between Ai1 and L enabled.
01
*1
*1. Default data when default data selection (UB-02) is set to 01.
02
Input between Ai2 and L enabled.
03
Input between Ai3 and L enabled.
04
Reserved
05
Reserved
06
Reserved
6-4-4
Case where Command Is Given through RS485 Communications
Item
Parameters
Data
Description
Default
data
Main speed input
source selection,
1st-motor
[AA101]
08
Command from RS485 communication
01
*1
*1. Default data when default data selection (UB-02) is set to 01.
6-4-5
Case where Command Is Given through Input of Pulse String
SW4
SW3
SW2
SW1
SW5
SW6
10V
20mA
10V
3
20mA
10V
2
20mA
10V
1
20mA
IN
5
EX
SINK
6
SRC
Ao2
Ao1
Ai2
Ai1
P.SEL
Ao2
Ao1
Ai2
Ai1
P SEL
((SW4) ((SW3)
((SW2) ((SW1)
((SW5) ((SW6)
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......