High-function General-purpose Inverter RX2 Series User’s Manual
Shown below are the multi-speed table for binary operation (when [Ab-03] = 00) and that for bit opera-
tion (when [Ab-03] = 01).
[Ab-03]=00.
Input terminal function 003 [CF1] to 006 [CF4]
[Ab-03] = 01; Input terminal function 007 [SF1] to 013 [SF7]
Table for Binary Operation
Multiple speeds
CF4
CF3
CF2
CF1
0th speed
OFF
OFF
OFF
OFF
1st speed
OFF
OFF
OFF
ON
2nd speed
OFF
OFF
ON
OFF
3rd speed
OFF
OFF
ON
ON
4th speed
OFF
ON
OFF
OFF
5th speed
OFF
ON
OFF
ON
6th speed
OFF
ON
ON
OFF
7th speed
OFF
ON
ON
ON
8th speed
ON
OFF
OFF
OFF
9th speed
ON
OFF
OFF
ON
10th speed
ON
OFF
ON
OFF
11th speed
ON
OFF
ON
ON
12th speed
ON
ON
OFF
OFF
13th speed
ON
ON
OFF
ON
14th speed
ON
ON
ON
OFF
15th speed
ON
ON
ON
ON
Table for Bit Operation
Multiple speeds
SF7
SF6
SF5
SF4
SF3
SF2
SF1
0th speed
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1st speed
-
-
-
-
-
-
ON
2nd speed
-
-
-
-
-
ON
OFF
3rd speed
-
-
-
-
ON
OFF
OFF
4th speed
-
-
-
ON
OFF
OFF
OFF
5th speed
-
-
ON
OFF
OFF
OFF
OFF
6th speed
-
ON
OFF
OFF
OFF
OFF
OFF
7th speed
ON
OFF
OFF
OFF
OFF
OFF
OFF
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......