7 - 51
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
3 T
orqu
e Con
tro
l
7
7-3
-4
Tor
que Limit
Functio
n
The output terminal 019 [OTQ] over torque signal will be turned ON when the output torque monitor
[dA-17] exceeds [CE120] to [CE123].
In the case of using as an under torque signal, output will be feasible when the output terminal a/b
[NO/NC] setting [CC-11] to [CC-17] corresponding to the output terminal function [CC-01] to [CC-07]
assigned with 019 [OTQ] is switched from 00 to 01.
To calculate the motor rated torque (100%) in this function, use the following formula.
Motor rated torque = 79.58 × Motor capacity × Number of poles/Base frequency
Example: Motor rated torque = 79.58 × 5.5 (kW) × 4 (P)/50 (Hz) ≈ 35 Nm
This level is used when you detect lift excessive high load.
Parameter
Output Terminal [CC-01] to [CC-07]
Over Torque Signal Output
Item
Parameter
Data
Description
Default
data
Over torque level
(Forward driving),
1st motor
[CE120]
0.0 to 500.0(%)
Turns On the [OTQ] output terminal function
when the output torque exceeds respective lev-
els.
100.0
Over torque level
(Reverse regener-
ative), 1st motor
[CE121]
Over torque level
(Reverse driving),
1st motor
[CE122]
Over torque level
(Forward regener-
ative), 1st motor
[CE123]
Item
Terminal name
Data
Description
Excessive torque
[OTQ]
019
A signal turns ON when it exceeds the over torque
level.
Torque
Powered
[CE120]
Regenerative
[CE121]
Reverse
Normal
Powered
[CE122]
Regenerative
[CE123]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......