7 - 59
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
4 Red
uct
ion
of Mo
to
r N
oise, N
oise an
d In
verter He
at Generat
ion
7
7-4
-1 Car
rier F
reque
ncy
7-4
Reduction of Motor Noise, Noise and
Inverter Heat Generation
The electromagnetic noise from the motor, noise from the inverter and the heat generation in the
inverter can be reduced/suppressed when you change the carrier frequency.
The carrier frequency is the frequency at which the element that controls the inverter output changes.
The carrier frequency can be changed using the [bb101] setting.
It is also effective in avoiding resonance of mechanical systems and motors.
Precautions for Correct Use
• With the selection using [Ub-03] Load specifications, the carrier frequency setting will be
automatically restrained.
• In accordance with the figures of
Derating of Rated Output Current
on page 2-10, operate the
inverter within the proper current range.
• If the [AA121] control method selection when driven by induction motor (IM) is automatic
torque boost (03), sensorless vector control (08), or zero speed area sensorless vector con-
trol (09), set the carrier frequency to 2.0 kHz or higher.
• If the [AA121] control method selection is the synchronous motor/permanent magnet motor
(SM/PMM) sensorless vector control (11), set the carrier frequency to 8.0 kHz or higher.
• The carrier frequency should be set to 10 times or higher of the [Hb105] IM highest frequency
or [Hd105] SM (PMM) highest frequency.
(Ex.) When [Hb105] = 60 Hz, [bb101] = 0.6 kHz (600 Hz) or higher
• When using the carrier frequency of 2.1 kHz or higher, see
2-1-3 Installation Environment
7-4-1
Carrier Frequency
Carrier Frequency and Its Extent of the Effect
Carrier frequency
Low
High
Motor electromag-
netic noise
Loud
Quiet
Noise
Quiet
Loud
Inverter heat gen-
eration
Little
Great
Leakage current
Low
High
Inverter output volt-
age waveform
example
(PWM output)
Carrier frequency: Low
Carrier frequency: High
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......