7 - 67
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
5 Start
Con
dit
ion
s
7
7-5
-3 F
requency Matching Star
t
Precautions for Correct Use
• If a power failure has occurred so that the power to the inverter’s control power supply termi-
nals (R0,T0) is lost, and then the inverter is restarted, it is considered as power-on and the
inverter will operate in accordance with the restart after reset [bb-41].
• Even if the power to control power supply terminals (R0, T0) is lost, it will take time until the
internal power supply is completely lost.
• Trip after instantaneous power failure/under-voltage can be switched between “enabled” and
“disabled” by using [bb-27] Selection of instantaneous power failure/under-voltage trip during
stopping. This will prevent the occurrence of an error during stopping. If the error is pre-
vented, the output terminal [AL] will not turn on.
• In a system where the power to control power supply terminals (R0, T0) gradually decreases,
it is possible to cause a trip when Allowable instantaneous power failure time has elapsed.
• To make the power to control power supply terminals (R0, T0) last as much as possible by
the inverter alone during an instantaneous power failure, remove the J51 connector cables
from terminals R0 and T0, and connect a cable from P on the main circuit terminal block to
R0, and N on the main circuit terminal block to T0. Use 0.75 mm
2
or heavier wires for the
connections.
(Ex.) Retry operation on overcurrent
(Ex.) Retry operation on overvoltage
Retry on Overcurrent [bb-28]=01
Item
Parameter
Data
Description
Default
data
Selection of restart
mode @over-cur-
rent
[bb-28]
01
Performs frequency matching restart.
01
Wait time of restart
@over-current
[bb-29]
0.3 to 100.0(s)
Sets the wait time after the retry operation on
overcurrent.
0.3
Retry on Overvoltage [bb-30]=01
0
[bb-29]
[bb-42]
Free-running
Restarting with frequency matching
Operation
command FW
Output current
Motor speed
Overcurrent occurs
0
[bb-31]
[bb-42]
Free-running
Restarting with frequency matching
Operation
command FW
Voltage between
P and N
Motor speed
Overvoltage occurs
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......