7 - 69
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
5 Start
Con
dit
ion
s
7
7-5
-4 F
requency Pull-in Start
To achieve these goals when the motor is idling due to a trip or terminal function, enable the frequency
pull-in function so that the inverter is started with the output frequency specified to each function.
Even if a motor residual voltage is lost, the inverter will restart at the frequency selected in [bb-47] Start
frequency selection for frequency pull-in restart.
When frequency pull-in with the V/f control is selected, the inverter starts with a suppressed output volt-
age during the time set for [bb-45] Frequency pull-in operation time (voltage). When sensorless vector
control, zero-speed range sensorless vector control, or vector control with sensor is selected, the fre-
quency is automatically pulled in while controlling the current.
If the current increases during frequency pull-in to exceed [bb-43] Restart level, the motor will
decelerate over the time set for [bb-44] Frequency pull-in operation time (frequency).
If the current rapidly increases during frequency pull-in to exceed [bb-46] Overcurrent suppression level
for frequency pull-in restart, the overcurrent suppression function will automatically set in.
(Ex.) How the frequency pull-in works
Precautions for Correct Use
• If the restart after free-run stop or the restart after reset is performed, the inverter will restart
after the retry wait time after instantaneous power failure/under-voltage has elapsed.
• The restart after free-run stop and the restart after reset will be performed when the operation
command is given.
• The frequency pull-in restart function can be used only for induced motor drive. In addition, if
[AA121] Control mode is set to other than the V/f control, restart may become unstable. In
this case, see
7-5-3 Frequency Matching Start
7-5-4
Frequency Pull-in Start
[bb-42]
[bb-43]
Free-running
Restarting with frequency pull-in
Retry wait time
Power failure
factor
Inverter output
frequency
Output current
Frequency pull-in
restart level
Deceleration time set at [bb-44]
Frequency set at [bb-47]
Lower limit
setting
Motor speed
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......