7 Advanced Settings
7 - 72
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.) Retry operation on overvoltage
(Ex.) Frequency matching operation after free-run stop [FRS]
Retry on Overvoltage [bb-30]=01
Item
Parameter
Data
Description
Default
data
Selection of restart
mode @over-volt-
age
[bb-30]
02
Performs frequency pull-in restart.
01
Wait time of restart
@over-voltage
[bb-31]
0.3 to 100.0(s)
Sets the wait time after the operation command.
0.3
Frequency Matching After Free-run Stop [FRS] [bb-40]=02
Item
Parameter
Data
Description
Default
data
Restart mode after
FRS release
[bb-40]
02
Performs frequency pull-in restart.
00
Retry wait time
before motor
restart
[bb-26]
0.3 to 100.0(s)
Sets the wait time after the operation command.
0.3
0
[bb-31]
[bb-42]
Free-running
Restarting with frequency pull-in
Operation
command FW
Voltage between
P and N
Motor speed
Overcurrent occurs
0
[bb-26]
[bb-42]
Free-running
Restarting with frequency pull-in
Operation
command FW
Free-run
stop FRS
Motor speed
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......