7 - 73
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
5 Start
Con
dit
ion
s
7
7-5
-5 Starting a
fter Power-on
(Ex.) Frequency matching operation after reset [RS]
Note If the frequency matching after reset has been set, starting after power-on will also occur with frequency
matching.
Sets the start mode at power-on.
(Ex.1) Restart operation with 0 Hz: [bb-41]=00
(Ex.2) Frequency pull-in operation [bb-41]=01 to 03
Frequency Matching After Reset [RS] [bb-41]=02
Item
Parameter
Data
Description
Default
data
Restart mode after
RS release
[bb-41]
02
Performs frequency pull-in restart.
00
Retry wait time
before motor
restart
[bb-26]
0.3 to 100.0(s)
Sets the wait time after the operation command.
0.3
7-5-5
Starting after Power-on
0
[bb-26]
[bb-42]
Free-running
Restarting with frequency pull-in
Operation
command FW
Reset RS
Motor speed
Restart with 0 Hz
Input power
Operation
command
Motor speed
[bb-26]
Free-running
Follows [bb-41]
Input power
Operation
command
Motor speed
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......