7 Advanced Settings
7 - 78
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.6) Frequency pull-in [bb-40]=01 to 03
Parameter
This function is to preliminarily establish magnetic flux by applying an excitation current via the forcing
terminal [FOC] command.
This function operates if the input terminal function 066 [FOC] is assigned.
Precautions for Correct Use
• This function is effective when the IM sensorless vector control, IM zero-speed range sensor-
less vector control, or IM vector control with sensor is selected for the control mode [AA121].
• If [FOC] is assigned to the input terminal function, operation will not be accepted unless
[FOC] is turned on.
• If [FOC] is turned off during operation, the inverter will be operated according to [AA115] Stop
mode selection. If a free run occurs, restart will take place according to the setting for the
restart after free-run stop.
Item
Parameter
Data
Description
Default
data
Restart mode after
FRS release
[bb-40]
00
Performs the 0 Hz restart.
00
01
Performs frequency matching restart.
*1
*1. See
7-5-3 Frequency Matching Start
02
Performs frequency pull-in restart.
*2
*2. See
03
Re-starts at the speed received from the Input
terminal A/B or from the PG Option Unit.
Retry wait time
before motor
restart
[bb-26]
0.3 to 100.0(s)
Sets the wait time after the power recovery.
0.3
STOP mode
selection,
1st-motor
[AA115]
01
Performs the free-run stop when the operation
command is off.
00
7-5-8
Forcing Function
[bb-26]
Operation
command
Motor speed
Free-running
Follows [bb-40]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......