7 - 79
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
5 Start
Con
dit
ion
s
7
7-5
-8 F
orcing
Function
• When [AA115] Stop mode selection is set to 00: Deceleration stop
• When [AA115] Stop mode selection is set to 01: Free run stop
Parameter
Precautions for Correct Use
• If torque at starting is insufficient, it may improve by adjusting the boost amount at starting
[HC111], [HC112] or the speed response [HA115].
• See
7-1 Overview of Motor Control Methods
• If torque at starting is insufficient, it may improve by using the torque bias function. See
Item
Parameter
Data
Description
Default
data
Input terminal func-
tion
[CA-01] to
[CA-11]
066
Forcing function [FOC]
-
STOP mode
selection,
1st-motor
[AA115]
00
Performs the deceleration stop when the opera-
tion command is off.
00
01
Performs the free-run when the operation com-
mand is off.
Restart mode after
FRS release
[bb-40]
00
Performs the 0 Hz restart.
00
01
Performs frequency matching restart.
*1
*1. See
7-5-3 Frequency Matching Start
02
Performs frequency pull-in restart.
*2
*2. See
Retry wait time
before motor
restart
[bb-26]
0.3 to 100.0(s)
Sets the wait time after the operation command.
0.3
FOC
FW
The inverter does not run
because FOC terminal =
OFF.
Output
frequency
Excitation
current flows.
Excitation current does
not flow.
Deceleration
stop
FOC
FW
Free-running
The inverter does not run
because FOC terminal =
OFF.
Output
frequency
Excitation
current flows.
Excitation current does
not flow.
Restart after free-run stop
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......