8 Applied Settings
8 - 4
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
PID Control
3G3RX2-series is equipped with 4 independent PID functions, and each PID can be set independently.
Four PID functions can be used for motor control by switching the [PIO1]/[PIO2] terminals.
PID not used for motor control can be used for operation of exterior PID not related to inverter control
freely.
This helps to save space and cost because there is no need to install a separate PID controller.
PID1 can be controlled based on 3 deviations.
Connecting PID1 and PID2 can make 2-layer PID control possible.
For PID control, you can select feed-forward control to attempt stabilizing disturbance in advance, in
addition to feedback control to stabilize disturbance.
To control output frequency sent to the motor by the PID function, selection of PID1-4 and setting of fre-
quency command are required.
In the soft-start function, operating normally for a certain period of distance at the start can raise output
automatically and then shift to PID control. See
Sleep operation, which is more energy saving, can be set for when the flow rate or air volume is
increased. See
During PID operation, PID functions are disabled and normal output is performed with the command
selected as a target value, while the input terminal function [PID] signal is ON.
Multi-layer command by PID control command is feasible.
8-1-1
Function Overview
PID1 target
value
MOTOR
PUMP
PID1
PID2
PID3
PID4
+
-
-
-
-
+
+
+
3G3RX2-series
PID2 target
value
PID3 target
value
PID4 target
value
Motor
Control
Exterior
equipment
Exterior
equipment
Exterior
equipment
Sensor
Sensor
Sensor
Pressure gauge
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......