8 - 9
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
P
ID Con
trol
8
8-1
-2 PID Par
ameter a
nd Block Dia
gram
Item
Parameter
Data
Description
Default
data
Input source selection
of Process data 1 for
PID1
[AH-51]
00 to 06,
08 to 13
00: Invalid, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved),
05: (Reserved), 06: (Reserved),
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option)
01
Input source selection
of Process data 2 for
PID1
[AH-52]
00 to 06,
08 to 13
00: Invalid, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved),
05: (Reserved), 06: (Reserved),
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option)
00
Input source selection
of Process data 3 for
PID1
[AH-53]
00 to 06,
08 to 13
00: Invalid, 01: Ai1-L input, 02: Ai2-L input,
03: Ai3-L input, 04: (Reserved),
05: (Reserved), 06: (Reserved),
08: RS 485 communication, 09: Option 1,
10: Option 2, 11: Option 3,
12: Pulse train input (main unit),
13: Pulse train input (option)
00
Calculation symbol
selection of Process
data for PID1
[AH-54]
01
(FB1)+(FB2)
01
02
(FB1)-(FB2)
03
(FB1)×(FB2)
04
(FB1)÷(FB2)
05
Square root of FB1
06
Square root of FB2
07
Square root of (FB1 - FB2)
08
Average of FB1/FB2/FB3
09
Minimum of FB1/FB2/FB3
10
Maximum of FB1/FB2/FB3
PID1 gain change
method selection
[AH-60]
00
Disable (gain 1 is used)
00
01
Switch by [PRO] terminal
PID1 proportional gain
1
[AH-61]
0.0 to 100.0
Proportional gain
1.0
PID1 integral time con-
stant 1
[AH-62]
0.0 to 3600.0(s) Integral gain
1.0
PID1 derivative gain 1
[AH-63]
0.00 to
100.00(s)
Differential gain
0.00
PID proportional gain 2
[AH-64]
0.0 to 100.0
Proportional gain
0.0
PID integral time con-
stant 2
[AH-65]
0.0 to 3600.0(s) Integral gain
0.0
PID1 derivative gain 2
[AH-66]
0.00 to
100.00(s)
Differential gain
0.00
PID1 gain change time
[AH-67]
0 to 10000(ms) Time for switch by [PRO] terminal operation
100
PID feed-forward
selection
[AH-70]
00
Disable
00
01
[Ai1] terminal input
02
[Ai2] terminal input
03
[Ai3] terminal input
04
(Reserved)
05
(Reserved)
06
(Reserved)
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......